wattstopper LMSW-105-CCT Скачать руководство пользователя страница 1

Wattstopper

 

®

Digital Lighting Management Low Voltage Correlated Color 

Temperature (CCT) Controller
Contrôleur de la température de couleur corrélée (TCC) de basse 

tension de gestion numérique de l’éclairage
Controlador de temperatura de color correlacionada (CCT) de bajo 

voltaje para el systema DLM

Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido

No: 24837 – 08/17  rev. 2

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMSW-105-CCT

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

SPECIFICATIONS

Voltage .............................................................................. 24VDC
Current Consumption .............................................................5mA
Power Supply ................Watt Stopper/Legrand Room Controllers
Connection to the DLM Local Network .................... 2 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx 

room controllers:
 

Low voltage power provided over Cat 5e cable (LMRJ);  

 

max current 800mA. Supports up to 64 load addresses,  

 

48 communicating devices including up to 4 LMRC-10x  

 

series and/or LMPL-101 controllers.  

 

Free topology up to 1,000’ max.

Environment ................................................. For Indoor Use Only
 

Operating Temperature .................32° to 131°F (0° to 55°C)

 

Storage Temperature ...................23° to 176°F (-5° to 80°C)

 

Relative Humidity .......................5 to 95% (non condensing)

Patent Pending

This unit is pre-set for Plug n’ Go™ operation, 

adjustment is optional.

For full operational details, adjustment and more features 

of the product, see the DLM System Installation Guide 

provided with Wattstopper room controllers, and also 

available at www.legrand.us/wattstopper.

Installation shall be in accordance with all applicable 

regulations, local and NEC codes. 

Wire connections shall 

be rated suitable for the wire size (lead and building wiring) 

employed. 

For Class 2 DLM devices and device wiring: To be 

connected to a Class 2 power source only. Do not reclassify 

and install as Class 1, or Power and Lighting Wiring.

Do not apply cleaning solvent directly onto unit. Apply 

cleaning solvent onto a cloth, then wipe the unit to clean it..

MOUNTING THE SWITCH

WARNING:

 Do not install to cover a junction box having Class 1, 3 or 

Power and Lighting Circuits.

BUTTONS AND INDICATORS

The rocker LED is always ON if the LMSW-105-CCT is 

bound to a load that is CCT enabled.
When the preset CCT Button level matches the CCT of the 

DLM network, the LED will be bright.

CONNECTIVITY AND WIRING

LMRJ Cables

LMSW-105-CCT

Preset Switch

Occupancy 

Sensor

LMTS-101-CCT

Schedule Switch

Daylighting Sensor

LMFC-RJ

DLM Cable Connector

LMLM-101 Mounted on

Araya or Blanco Logic Module

 

LMPB-100

Power

Booster

J-Box

120/277VAC

NOTE: Each DLM local network must include a 

            DLM room controller, relay panel, or power booster

            to supply low voltage power to the LMLM-101.

Red

Black

Blue

Red LED

Blue Status LEDs

Preset CCT Buttons (4)

Configuration Button 

(behind switch plate)

Press and Hold to ramp

through CCT levels

The illustration shows an example of 

free-topology wiring. The LMSW-105-CCT 

communicates with all other Digital Lighting 

Management devices connected to the low 

voltage DLM Local Network. 

Содержание LMSW-105-CCT

Страница 1: ...attstopper room controllers and also available at www legrand us wattstopper Installation shall be in accordance with all applicable regulations local and NEC codes Wire connections shall be rated suitable for the wire size lead and building wiring employed For Class 2 DLM devices and device wiring To be connected to a Class 2 power source only Do not reclassify and install as Class 1 or Power and...

Страница 2: ...s ON 2 To unbind a button from a load press the button while its blue LED is ON The blue LED turns OFF to indicate the button no longer controls the load that is currently ON On the scene switch unbinding a load from a scene button removes it from the scene so that when the scene activates the load s state does not change 3 Pressing the switch button again while the load is ON rebinds the load to ...

Страница 3: ...lisé Pour les dispositifs DLM de classe 2 et le câblage du dispositif Doit être connecté à une source d alimentation de classe 2 seulement Ne pas reclasser et installer en tant que classe 1 ou en tant que fil d alimentation ou d éclairage Ne pas appliquer de solvant de nettoyage directement sur l appareil Appliquer le solvant de nettoyage sur un chiffon et frotter l appareil pour le nettoyer MONTA...

Страница 4: ... s ÉTEINT pour indiquer que le bouton ne contrôle désormais plus la charge qui est actuellement ALLUMÉE Pour empêcher un dispositif d éclairage de s allumer couper le lien entre une charge et un bouton d ambiance sur un bouton d ambiance ainsi l état de charge ne sera pas modifié 3 En appuyant sur le bouton de l interrupteur à nouveau pendant que la charge est ALLUMÉE la charge sera à nouveau liée...

Страница 5: ...ción para cubrir una caja de conexiones con circuitos de alimentación e iluminación o de Clase 1 3 BOTONES E INDICADORES El LED basculante está siempre encendido si el dispositivo LMSW 105 CCT está vinculado a una carga que está habilitada para CCT Cuando el nivel del Botón CCT preestablecido coincida con el CCT de la red DLM el LED brillará CONECTIVIDAD Y CABLEADO La ilustración siguiente muestra...

Страница 6: ...espués de un segundo se encenderá una carga Esta es la carga N 1 que está vinculada con la paleta del LMSW 105 CCT y con todos los botones como parte de la configuración predeterminada de fábrica de Plug n Go El LED azul se mostrará encendido en todos los botones del interruptor los atenuadores los botones de escena y los sensores vinculados a esta carga Paso 2 Selección de carga 1 Presione y suel...