Sensor Parameters

Time Delay 

20 minutes

Passive Infrared 

Sensitivty

90%

Ultrasonic 
Sensitivity

70%

Walk Through

OFF

Initial Occupancy

PIR and    

Ultrasonic

Maintain Occupancy

PIR or  

Ultrasonic

2/2012 

15006

r3

Please 

Recycle

2800 De La Cruz Blvd.  

Santa Clara, CA 95050 

Phone: 800.879.8585 

www.wattstopper.com

TROUBLESHOOTING

Loads do not operate as expected.

LEDs don’t light, display is off

1.  Check to see that the sensor is connected to the DLM local Network.
2.  Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location. If the 

device does not power up, 24VDC is not present.

•  Check the high voltage connections to the room controller.
•  If high voltage connections are good and high voltage is present, recheck DLM local Network 

connections between the sensor and the room controller.

The wrong lights are controlled

1.  Configure the sensor to control the desired lights using the Push n’ Learn adjustment procedure. 

LEDs turn ON and OFF but load 

doesn’t switch

1.  Make sure device is not in PnL.
2.  Check load connections to room controller.

WARNING:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE 

LMCI-100.  

NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT

 

– DOING SO MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

PLUG n’ GO OPERATION (PnG)

Each load is automatically assigned to a switch button.        

  If there is only one load it will default to Manual ON/Auto OFF. If there is more than one load then the first load 

will default to Auto ON/Auto OFF and the rest of the loads will default to Manual ON/Auto OFF.

  If there are 

more buttons

 on a switch than there are loads, the extra button(s) do nothing and blink when pressed.

• 

If there are 

fewer buttons

 on a switch than there are loads, the last button controls all remaining loads.

UNIT ADJUSTMENT - PUSH n’ LEARN (PnL)

Load Selection Procedure

A configuration button allows access to our patented Push n’ Learn™ technology to change the binding relationship between switch buttons and loads.

Step 1: Enter Push n’ Learn

Using a pointed tool, press and hold the configuration button for 3 seconds, until the Red LED on the switch begins to blink. 

 

         When you release the switch’s configuration button, the red LED on other communicating DLM Local Network devices begins to blink. 
 

The DLM Local Network is now in PnL mode. The Red LEDs continue to blink until you exit PnL mode.

 

All loads in the room turn OFF after entering PnL. After one second, one load turns ON. This is Load #1, which is bound to switch button #1 as part 

of the  Plug n’ Go factory default setting. 

The Blue LED will be ON for all switch buttons and sensors that are bound to this load.

Step 2: Load selection

 

Press and release the configuration button to step through the loads connected to the DLM Local Network. As each load turns ON note which 

devices (switch buttons and sensors) are showing the blue LED. These devices are currently bound to the load that is ON.

 To 

unbind

 a switch button from a load, press the switch button while its blue LED is ON. The blue LED turns OFF to indicate the button no longer 

controls the load that is currently ON.  Use the up and down arrow to bind and unbind the sensor.

 

Pressing the switch button again while the load is ON 

rebinds

 the load to the button and the blue LED illuminates.

Step 3: Exit Push n’ Learn

 

Press and hold the configuration button until the red LED turns off, approximately 3 seconds.

RELEASING LENS

Insert a small paper clip into the small hole at the top of the trim ring. Press in firmly until the lens is released and springs forward. Grab the lens and 

remove it completely to expose the screen.

LCD
Screen

REINSERTING LENS

Reinsert the lens in the proper orientation: place the two posts at the bottom at a 30 degree 

angle with the chamfered edge facing up. Gently press the top of the lens until it locks in 

place.