Sensor Parameters
Time Delay
20 minutes
Passive Infrared
Sensitivty
90%
Ultrasonic
Sensitivity
70%
Walk Through
OFF
Initial Occupancy
PIR and
Ultrasonic
Maintain Occupancy
PIR or
Ultrasonic
2/2012
15006
r3
Please
Recycle
2800 De La Cruz Blvd.
Santa Clara, CA 95050
Phone: 800.879.8585
www.wattstopper.com
TROUBLESHOOTING
Loads do not operate as expected.
LEDs don’t light, display is off
1. Check to see that the sensor is connected to the DLM local Network.
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location. If the
device does not power up, 24VDC is not present.
• Check the high voltage connections to the room controller.
• If high voltage connections are good and high voltage is present, recheck DLM local Network
connections between the sensor and the room controller.
The wrong lights are controlled
1. Configure the sensor to control the desired lights using the Push n’ Learn adjustment procedure.
LEDs turn ON and OFF but load
doesn’t switch
1. Make sure device is not in PnL.
2. Check load connections to room controller.
WARNING:
TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE
LMCI-100.
NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT
– DOING SO MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.
PLUG n’ GO OPERATION (PnG)
Each load is automatically assigned to a switch button.
•
If there is only one load it will default to Manual ON/Auto OFF. If there is more than one load then the first load
will default to Auto ON/Auto OFF and the rest of the loads will default to Manual ON/Auto OFF.
•
If there are
more buttons
on a switch than there are loads, the extra button(s) do nothing and blink when pressed.
•
If there are
fewer buttons
on a switch than there are loads, the last button controls all remaining loads.
UNIT ADJUSTMENT - PUSH n’ LEARN (PnL)
Load Selection Procedure
A configuration button allows access to our patented Push n’ Learn™ technology to change the binding relationship between switch buttons and loads.
Step 1: Enter Push n’ Learn
Using a pointed tool, press and hold the configuration button for 3 seconds, until the Red LED on the switch begins to blink.
When you release the switch’s configuration button, the red LED on other communicating DLM Local Network devices begins to blink.
The DLM Local Network is now in PnL mode. The Red LEDs continue to blink until you exit PnL mode.
All loads in the room turn OFF after entering PnL. After one second, one load turns ON. This is Load #1, which is bound to switch button #1 as part
of the Plug n’ Go factory default setting.
The Blue LED will be ON for all switch buttons and sensors that are bound to this load.
Step 2: Load selection
Press and release the configuration button to step through the loads connected to the DLM Local Network. As each load turns ON note which
devices (switch buttons and sensors) are showing the blue LED. These devices are currently bound to the load that is ON.
To
unbind
a switch button from a load, press the switch button while its blue LED is ON. The blue LED turns OFF to indicate the button no longer
controls the load that is currently ON. Use the up and down arrow to bind and unbind the sensor.
Pressing the switch button again while the load is ON
rebinds
the load to the button and the blue LED illuminates.
Step 3: Exit Push n’ Learn
Press and hold the configuration button until the red LED turns off, approximately 3 seconds.
RELEASING LENS
Insert a small paper clip into the small hole at the top of the trim ring. Press in firmly until the lens is released and springs forward. Grab the lens and
remove it completely to expose the screen.
LCD
Screen
REINSERTING LENS
Reinsert the lens in the proper orientation: place the two posts at the bottom at a 30 degree
angle with the chamfered edge facing up. Gently press the top of the lens until it locks in
place.