WIRING AND INSTALLATION
The EW-205-24 can be powered from either a WattStopper Power Pack, or a WattStopper HID
Dimming Module.
•
Each WattStopper B series power pack can supply power for up to 11 sensors.
•
Each WattStopper BZ series power pack can supply power for up to 15 sensors.
•
Each DM-105 or DM-115-WP module can supply power for up to 2 sensors.
When power is initially applied to the sensor, or following restoration from a power failure, the
lights will turn on. If no motion is detected by the sensor, the lights will remain on/high for for
approximately one minute and then turn off/low. (See Security Override, page 9.)
Sensor Wire Functions
The EW-205-24 has 3 wire connections to the power pack or DM-105 or DM-115 -WP module.
See the descriptions and wiring diagrams that follow for connections to each specific power
source.
RED: +24VDC input to sensor
BLACK: Common
BLUE: +24VDC control output from sensor
CAUTION
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING SENSOR .
SENSOR MUST BE INSTALLED BY QUALIFIED PERSONNEL ONLY .
4" round
outdoor
junction box
Cover plate
To Power Pack or HID
Dimming Module
5
RED
BLACK
BLUE
Attach cover plate assembly and gasket to
the junction box with 4 screws and screw
covers (supplied)
IMPORTANT!
Make sure that the gasket
seats properly when attaching the cover
plate
IMPORTANT!
Thread wires through
gasket before connecting
NOTE:
Weather proof caulking may be required around
junction box and cover plate to provide a weatherproof seal in
some installations.