background image

Call 800.879.8585 for Technical Support

SENSOR OPERATING MODES

Sensor #1 Sensor #2

Light Fixture

Auto-ON

Auto-ON

The load turns 

ON

 and 

OFF

 automatically based 

on occupancy detection by either one of the 

sensors. The sensors keep the load 

ON

 until no 

motion is detected and will use the time delay 

of the sensor with the lowest value. At any time, 

the light can be turned ON and 

OFF

 using the 

ON/OFF

 button of any one of the sensors. If the 

load is turned 

OFF

 manually by pressing either 

one of the 

ON/OFF

 buttons, the unit will enter 

Presentation mode.

Auto-ON*

Manual ON* The load can only be turned 

ON

 automatically by 

the sensor set in 

Auto-ON

 mode. The sensors 

keep the load ON until no motion is detected 

and will use the time delay of the sensor with 

the lowest value. There is either a 30 second 

re-trigger delay for the sensor set in 

Manual-

ON

 mode or instant re-trigger for the sensor 

set in 

Auto-ON

 mode. After the re-trigger delay 

elapses, the 

ON/OFF

 

button of the sensor set in 

Manual-ON

 mode must be pressed to turn the 

load back on unless the sensor set in 

Auto-ON

 

mode detects motion. If the light is turned 

OFF

 

manualy by pressing the 

ON/OFF

 button set in 

Auto-ON

, it will enter Presentation mode.

Manual-ON

Manual-ON

The occupant must press the 

ON/OFF

 button on 

either one of the sensors to turn the light 

ON

The sensors keep the load 

ON

 until no motion 

is detected and will use the time delay of the 

sensor with the lowest value. There is a 30 

second re-trigger delay, meaning the occupant 

has 30 seconds to be detected for the sensor to 

turn the load back on automatically. After the 

re-trigger delay elapses, the 

ON/OFF

 button of 

any one of the sensors must be pressed to turn 

the load back 

ON

.

* Although this configuration may be selected, it is not recommended.

Содержание DSW-301

Страница 1: ...347 VAC 1500 W ballast LED 1 4 HP Load Limits for relay 2 120 VAC 800 W tungsten ballast E ballast LED 1 6 HP 277 VAC 1200 W ballast E ballast LED 1 6 HP 347 VAC 1500 W ballast LED 1 6 HP Time Delay...

Страница 2: ...responding relay Optional Neutral is also available on all models DSW sensors contain a light level sensor If adequate daylight is present the sensor holds the load OFF until light levels drop even if...

Страница 3: ...SETTINGS for more information Test 20 min DIP 1 2 OFF A Test Mode with a short time delay of five seconds is set when DIP switches 1 2 are OFF It cancels automatically after ten minutes or when you s...

Страница 4: ...No audible warnings provided Trigger Mode The DSW sensor has four occupancy trigger options set with DIP switches 5 and 6 Determine the appropriate option using the Trigger matrix In the Trigger Mode...

Страница 5: ...sensitivity can be adjusted using the trimpot under the ON OFF buttons PIR Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Ultrasonic Coverage 10 3 0m 7 5 2 2m 13 4 0m 10 3 0m Ma...

Страница 6: ...will not hold the light OFF INSTALLATION WARNING TURN OFF THE POWER AT THE CIRCUIT BREAKER BEFORE INSTALLING THE SENOR WORKING ON THE LOAD 1 Make sure that the power has been turned OFF at the circui...

Страница 7: ...away tab 8 flying leads for line load ground and multi way connections DSW 302 shown The DSW 301 does not include these two leads Yellow Red Green Black Brown Blue Neutral Optional Wiring MULTI WAY Th...

Страница 8: ...utral Neutral optional Line Yellow Red Primary Load Brown Secondary Load Neutral optional Ground Green Ground Green Red Brown Blue Blue Bi level Wiring DSW 302 or DSW 302 347 up to 4 sensors Note Butt...

Страница 9: ...a 30 second re trigger delay for the sensor set in Manual ON mode or instant re trigger for the sensor set in Auto ON mode After the re trigger delay elapses the ON OFF button of the sensor set in Man...

Страница 10: ...ancy Re trigger seconds duration Option C Both Both Both 5 Standard Either 5 Either Option A Either Either 5 PIR Both Option B PIR PIR PIR 5 3 Disabled Enabled Walk Through Trigger Mode DSW 302 ONLY O...

Страница 11: ...support Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify proper operation set DIP switch 1 to ON then reset switches 1 and 2 to OFF to st...

Страница 12: ...al damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property revenue or profit or cost of removal installation or r...

Отзывы: