background image

Call 800.879.8585 for Technical Support

BI-LEVEL CONTROL

The diagram to the right 

shows how to configure 

BZ-2xx to provide bi-level 

lighting control with both 

Automatic ON and Manual 

ON features.
As shown, upon occupancy 

detection load A turns 

ON

 automatically. To turn 

ON

 load B, the user must 

press momentary switch 

B. Both loads turn OFF 

automatically when the 

sensor time delay expires, 

or manually using switch 

A and B. If the sensor 

input re-triggers within 

30 seconds after the load 

turns 

OFF

, loads A and B 

turn 

ON

 again. After 30 

seconds expire with no 

sensor input, you must 

press the switch to turn 

ON

 load B.

LOW VOLTAGE OUTPUT OVERLOAD PROTECTION

The BZ-2xx contains built-in short circuit and thermal protection circuitry that 

shuts down the +24 VDC output (low voltage red wire) to prevent permanent 

damage to the power pack. Removing the excess load from the output restores 

the BZ-2xx to proper operation. Connect the excess load to another power pack.
Output is current limited. As the load increases, the BZ output will reach its 

model-specific maximum output current. Under these conditions, the output 

voltage may appear less then the nominal 24-V output and the BZ will indicate 

the overload conditions with a continuously blinking LED (as described in the LED 

Indicator section). In extreme cases, such as a dead short, the output voltage will 

appear near zero but will automatically return to normal operating conditions 

once the excess load is removed.  

+24VDC

Common

Red

White

Neut.

BZ-2xx

(A)

AUTO ON

Blue

Black

Red

Lighting

Load (A)

Black

Any 3-Wire

24VDC

Sensor 

Hot

Red

Brown

Orange

Control

Low Voltage Wires

Red

White

Neut.

BZ-2xx

(B)

MANUAL ON

Blue

Black

Red

Lighting

Load (B)

Black

Hot

Red

Brown

Orange

Gr

ey

Momentary Switch (B)

Low Voltage Wires

Gr

ey

Momentary Switch (A)

Ground

Ground

NOTES:

• Orange, Brown, and Grey wires 

are applicable only to the 
BZ-250 and BZ-250-347.

• BZ-2xx power packs should be 

grounded to ensure signal 
integrity, not for safety ground.

Parallel interconnect for bi-level load control 

from a single sensor with manual ON

Содержание BZ-2 Series

Страница 1: ...277 VAC BZ 250 347 16 A 120 347 VAC E Ballast CFL 16 A 120 277 VAC Motor BZ 200 BZ 250 1 HP 120 240 VAC BZ 250 347 1 4 HP 120 347 VAC Plug Load BZ 200 BZ 250 20 A 120 VAC BZ 250 347 15 A 120 VAC Class 2 Output BZ 200 w relay connected 225 mA 24 VDC BZ 250 BZ 250 347 225 mA 24 VDC Low Voltage Input Control ON 5 30 VDC Operating Temperature 4 131 F 20 55 C Storage Temperature 40 176 F 40 80 C UL C U...

Страница 2: ...ensors and other control devices INSTALLATION Wiring 1 Make sure power has been turned off at the circuit breaker 2 Connect wires as shown in the wiring diagram below or as shown in the BI LEVEL CONTROL section 24VDC Common Red White Neut BZ 2xx Blue Black Red Dry Contact Lighting Load Black 5 30 VDC In Hold OFF 5 30 VDC In Hold ON Any 3 Wire 24VDC Sensor Hot Red Brown Orange Grey Control Momentar...

Страница 3: ...manually from an optional low voltage momentary switch See the section on Low Voltage Inputs for details Auto ON Manual ON Slide Switch BZ 250 BZ 250 347 only Use the Mode Switch to select either the Auto ON mode or the Manual ON mode The mode will take effect within two seconds Auto ON Mode Switch UP default The occupancy sensor input Hold ON input and the optional momentary switch input can all ...

Страница 4: ...cation See the WIRING section for wiring information Control Inputs Control ON Blue wire This input is intended for occupancy sensor input Applying 5 30 VDC closes the relay in Auto ON Mode Remove the voltage and the relay opens if no other input is holding it closed Hold ON Orange wire BZ 250 BZ 250 347 only This input is intended for timer or panel input Applying 5 30 VDC closes the relay in Aut...

Страница 5: ... the excess load to another power pack Output is current limited As the load increases the BZ output will reach its model specific maximum output current Under these conditions the output voltage may appear less then the nominal 24 V output and the BZ will indicate the overload conditions with a continuously blinking LED as described in the LED Indicator section In extreme cases such as a dead sho...

Страница 6: ...e load does not turn ON with occupancy detection Mode Switch is set to Manual ON Hold OFF input is active The load does not turn OFF after sensor time delay expires Hold ON input is active Check sensitivity on the occupancy sensor Verify that the time amount is the intended amount Verify that the sensor is not being retriggered by unintentional movement or byplacement too close to a an air vent Th...

Страница 7: ...ad Rating Ballast A 20 20 16 Incandescent A 20 20 16 Motor hp 1 1 1 4 Plug Load 20 A 120 240 VAC 20 A 120 240 VAC 15A 120 240 VAC Output 24 VDC 225 mA w relay connected 24 VDC 225 mA 24 VDC 225 mA Auto Manual ON Slide Switch No Yes Yes Control Inputs Control ON Yes Yes Yes Hold ON No Yes Yes Hold OFF No Yes Yes Momentary Input Manual ON OFF No Yes Yes Override Button Yes Yes Yes Power Loss Mode No...

Страница 8: ...be free of defects in materials and workmanship for a period of five 5 years There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property revenue or profit or cost of removal installation or reinstallation ...

Отзывы: