Parameters 

Installer’s Advanced Menu 

number 

names 

Description of the parameter 

Factory value 

Other possibility 

10 

LanG 

Selection the language for the both parameters menus. 

GB

” 

English 

Fr

” 

French 

11 

Air.S 

View of the measured values of the ambient sensor.  

__._

   

12 

OUT.S 

View of the measured values of the floor (external) 
sensor.  

__._

  

13 

FL.Lo 

Lower limit of the floor temperature.  

no

” 

The lower 

limitation is not 

used 

From 5°C to 

FL.Hi

                   

14 

FL.Hi 

Upper limit of the floor temperature.  

no

” 

The upper 

limitation is not 

used

 

From 

FL.Lo

 to 37°C 

15 

regu 

Selection of regulation type 

pwm

” 

 

Proportional 

band (PWM) 

hys

” 

 

0,5°C Hysteresis (On/Off) 

16 

t.Cy 

Selection of the proportional band duration in minutes 
(cycle duration) 

10

” 

 

Ideal value for 

all Electrical 

floors heating 

application. 

You could increase this 

value if the thermostat is 

used for other heating 

application (Oil Boiler...) 

17 

t.on 

Minimal starting time in minutes 

002

” 

Adjustable  

0

 to

 

T cy

/2

 

18 

t.off 

Minimal resting time between 2 heating cycles in minutes  

002

 

Adjustable  

0

 to

 

T cy

/2

 

19 

Pwm.v 

Value of the proportional band in °C 

Note:  

If the value of proportional band is too big the system 
reactivity will be slower and could affect the steps of the 
program. 

3.0

” 

Ideal value for 

all Electrical 

floors heating 

application. 

Adjustable  

1

 to

 

6.0

 

A well insulated house 

« 

1.5°C»

 

A not insulated house 

« 

4°C

 » 

20 

Cp 

Compensating value of the regulation 
 
This value will need to be modified only if the thermostat 
is perturbed by the heating element. 
Generally never the case with electrical floor heating. 

00.0

” 

Adjustable  

0

 to

 

14.0

 

Increase this value if the 

thermostat is too close to 

the heating source. 

21 

Clr EEp 

All parameters will be reloaded with the factory value. 

Press on the 

(OK) 

key

 

during few seconds. 

22 

End 

To exit the installer‟s menu 

Press on the 

(OK) 

to exit. 

 