Parameters
Installer’s Advanced Menu
number
names
Description of the parameter
Factory value
Other possibility
10
LanG
Selection the language for the both parameters menus.
“
GB
”
English
“
Fr
”
French
11
Air.S
View of the measured values of the ambient sensor.
“
__._
”
12
OUT.S
View of the measured values of the floor (external)
sensor.
“
__._
”
13
FL.Lo
Lower limit of the floor temperature.
“
no
”
The lower
limitation is not
used
From 5°C to
“
FL.Hi
”
14
FL.Hi
Upper limit of the floor temperature.
“
no
”
The upper
limitation is not
used
From
“
FL.Lo
”
to 37°C
15
regu
Selection of regulation type
“
pwm
”
Proportional
band (PWM)
“
hys
”
0,5°C Hysteresis (On/Off)
16
t.Cy
Selection of the proportional band duration in minutes
(cycle duration)
“
10
”
Ideal value for
all Electrical
floors heating
application.
You could increase this
value if the thermostat is
used for other heating
application (Oil Boiler...)
17
t.on
Minimal starting time in minutes
“
002
”
Adjustable
“
0
”
to
T cy
/2
18
t.off
Minimal resting time between 2 heating cycles in minutes
“
002
”
Adjustable
“
0
”
to
T cy
/2
19
Pwm.v
Value of the proportional band in °C
Note:
If the value of proportional band is too big the system
reactivity will be slower and could affect the steps of the
program.
“
3.0
”
Ideal value for
all Electrical
floors heating
application.
Adjustable
“
1
”
to
“
6.0
”
A well insulated house
«
1.5°C»
A not insulated house
«
4°C
»
20
Cp
Compensating value of the regulation
This value will need to be modified only if the thermostat
is perturbed by the heating element.
Generally never the case with electrical floor heating.
“
00.0
”
Adjustable
“
0
”
to
“
14.0
”
Increase this value if the
thermostat is too close to
the heating source.
21
Clr EEp
All parameters will be reloaded with the factory value.
Press on the
(OK)
key
during few seconds.
22
End
To exit the installer‟s menu
Press on the
(OK)
to exit.