USER GUIDE 

GB 

INSTALLATION PARAMETERS MENUS 

Dual Sensing Digital Thermostat 230Vac WFHT  041 (20425)

MODES DESCRIPTION 

Electronic thermostat with LCD display mode for water floor heating 
systems controlled by actuators. 

- External 

pilot 

wire 

for night reduction. 

Three Functioning modes: Comfort, reduction or Clock mode. 

Possibility to regulate either the floor or room temperature, or combined 
(in this case, the floor sensor is used as temperature limiter) 

Silent (triac output), to be connected directly to actuators (see connecting 
drawing on the installation sheet) or to our Modular connecting system. 
(In this case please refer to the connecting box datasheet)

PPL IMP 1111A  

Measured temperature precision 

0.1°C  (or 0.2°F) 

Operating temperature 

0°C - 50°C  (or 32°F – 122°F) 

Setting temperature range 

5°C - 37°C by 0.5°C step                                                       
(or 41°F - 99°F by 0.5°F step) 

Regulation characteristics 

Proportional Integral regulation (adjustable see installation 
menu) Cycle: 15 minutes or 
Static differential 0.3°K 
Anti-short cycle: 3min in OFF, 2min in ON. 

Electrical Protection 

Class II   -   IP30 

Power Supply 

230 VAC +/- 10% 

Output 

TRIAC output 230 VAC, 75 W max.  
( 15 actuators WATTS 22C type)                    

External Floor sensor 

NTC (10K Ohms) 3m 

TECHNICAL CHARACTERISTICS 

DISPLAY 

 

Press the 

OK key during 5 seconds

,

 

Then use 

+

 or 

-

 keys to select the installation parameter to be adjusted.

 

 
Press 

OK

 to toggle the parameter setting or edit the value. If the value starts to blink you can use 

-

 keys to adjust 

this value. Press 

+

 & 

-

 keys at the same time to reset this value to the factory default value. Once you have adjusted 

the value press 

OK

 to validate this parameter value. 

When you have finished, use 

+

 / 

-

 keys to go to ‘End’ display and then press 

OK

 key to exit installation parameter 

menu.

 

 
J0 :

 °C / °F temperature display selection 

J1 :

 “Hot” / “Cold” regulation mode. Select Hot for a Heater system, select Cold for a Cooling system 

Cy :

 

Proportional Integral regulation time cycle value in minutes (default: 15 minutes cycle) 

bp :

 

Proportional Integral regulation band amplitude value in degrees  °C/°F (default: 2.0°C/3.6°F) 

J4:

  

“NC” or “NO” Normally closed or normally open actuators selection. 

J5 :

 Select 

“PMP” to perform an 1 minute exercise everyday (if installation inactive during a day)  

J6 :

 Air or Floor temperature regulation selection. (if no Floor sensor, regulation will use Air sensor) 

J7 :

 “rEG” (Proportional Integral) or “HYs” (0.3°K Hysteresis) regulation type selection 

Cp :

 

compensation value in °C/°F (default: 2.0°C/3.6°F) this parameter must be adjusted by a professional. 

Ao :

 

Air sensor offset adjustment (default: no offset). Display measured Air sensor value 

Fo :

 

Floor sensor offset adjustment (default: no offset). Display measured Floor sensor value 

FL :

 

Floor temperature LOW limitation (default: 5°C/41°F), effective only if floor sensor present 

FH :

 

Floor temperature HIGH limitation (default: 28°C/82°F) , effective only if floor sensor present 

CLr :

 Press 

OK

 key during 5s to reset all the WFHT LCD parameters to factory defaults 

End :

 Press 

OK

 key to exit installation parameter menu and return to normal operation 

 
* (Default parameters are underlined.)

 

 

COMFORT operating mode: 

 
Force comfort temperature operation 
indefinitely. 
By pr/- keys the comfort 
temperature starts to blink and can be 
adjusted. 
The measured        temperature    
reappears after a few seconds. 
    
 
       

OFF mode: 

 

Use this mode if your Heating 
installation needs to be turned OFF. 
The display is blank. 
(Careful in this mode your installation 
can freeze) 
Parameters are saved. 

 

  REDUCED operating mode: 

 

Force reduced temperature operation 
indefinitely. 
By pr/- keys the comfort 
temperature starts to blink and can be 
adjusted. 
The measured         temperature      
reappears after a few seconds. 
 

  External PILOT WIRE mode: 

 

The Thermostat will follow the external 
PILOT WIRE signal. 
 

  Blinking for indicate a comfort signal. 

 

  Blinking for indicate a reduced signal. 

 

Use 

OK

 key to change the mode in the Operating mode menu 

1:

   Operating mode menu. 

2:

   Heating indication. 

3:   

Cooling indication. 

4:

   If symbol is displayed the measured temperature 

is shown (position 5) 

5:

   Measured temperature or set temperature. 

6:

   °C or °F indication. 

7:   

Title for installation Parameters (J0,CLr…) 

 