The following tests are to be performed using standard 
testing practices and procedures and should only be car-
ried out by properly trained and experienced persons.
A good quality electrical test meter, capable of reading 
from at least 0-300 V (ac), 0-30 V (dc), 0-2,000,000 
Ohms, and testing for continuity is essential to properly 
test the wiring and sensors.

Test Meter

Control Terminals

Testing the Power

1.  Remove the front and wiring covers from the control.
2.  Use an electrical test meter to measure (ac) voltage 

between the Power N and L terminals (1 and 2). The 
reading should be 115 V (ac) + / – 10%. The Power 
LED should be on.

3.  If power is not present the Power LED will be off. 

Check the circuit(s) that supply power to the Power  
N and L terminals (1 and 2).

Testing the tN4 Buses

 1.  Remove the front and wiring covers from the control.
 2.  There are a total of five tN4 buses (tN4 and C).  

The corresponding tN4 LED will be on if there is  
communication on the tN4 bus.

 3.  If there is no communication on a tN4 bus that is  

supposed to have communication, there may an  
open or short circuit. An open or short circuit will be 
indicated as a bus error on any tN4 thermostats, tN4 
setpoint controls, and tN4 system controls.

 4.  To test for short circuits:

•  Disconnect the tN4 bus wires on both ends.
•  Install wire nuts on each wire on one end to ensure 

the wire ends are not touching.

•  Measure for continuity using an electrical meter.
•  If continuity is present, there is a short circuit fault 

along the wires. It is recommended to replace the  
tN4 bus wires.

 5. To test for open circuits:

•  Disconnect the tN4 bus wires on one end and  

connect them together.

•  Disconnect the tN4 bus wires on the other end.
•  Use an electrical meter to measure for continuity.
•  If there is no continuity, there is an open circuit fault 

along the wires. It is recommended to replace the  
tN4 bus wires.

Testing the RS 232 Serial Port

A terminal shell called Termite can be used to test the RS 
232 serial port hexadecimal data.

Step 1:

 Download the Termite (complete setup) terminal 

program for Windows.
http://www.compuphase.com/software_termite.htm

Step 2:

 Settings

Baud rate = 9600, Data bits = 8, Stop bits = 1,  
Parity = none, Flow control = none, Forward = none
Hex View = check marked

Step 3:

 Enter commands

Hexadecimal values can be entered in the command line 
at the bottom. The hexadecimal numbers must be entered 
in the format 0x00 followed by a space.
The 482 includes a built-in test routine that transmits a 
message via the RS232 port. The result of this is that the 
Tx indicator will flash as the message is sent.
Start the test routine by pressing the Test button for  
1 second. The Test LED turns red.

The RS232 message includes the following:
 1.  FirmwareRevision
0xca 0x07 0x06 0x02 0x87 0x01 0x00 0x00 

0x91

 0x00 

0x28 0x35
This means that the 482 firmware version is 6c hexadecimal 
or 145 in decimal.
 2.  ProtocolVersion
0xca 0x07 0x06 0x02 0x8f 0x01 0x00 0x00 

0x02

 0x00 

0xa1 0x35
The means that the 482 protocol version is 02.
The 482 then exits the test routine and resumes normal 
operation.

Troubleshooting the Wiring 

 

     General   

Testing the Control 

 

Содержание TekmarNet 4

Страница 1: ...ion systems Features Installation Operation and Maintenance Manual tekmarNet 4 Gateway 482 IOM T 482 tekmarNet 4 and tekmarNet 2 Compatible CSA C US approved for US and Canada Drivers available for these third party automation systems AMX Clare Controls Control4 Crestron Elan RTI Savant URC and Vantage home automation systems Trademarks are the property of their respective third party WARNING Plea...

Страница 2: ... length of each tN4 bus cannot exceed 5000 feet Each tN4 bus consists of a pair of wires tN4 and C The tN4 Gateway can accept up to 5 tN4 buses Use a Category 5 cable up to or less than 150 feet 45 m in length to connect the tN4 Gateway to the home automation equipment To avoid serious personal injury and damage to the equipment Improper installation and operation of this control could result in d...

Страница 3: ...rol mount it onto the DIN rail This will be a popular option for those who pre fer to mount the control inside a larger electrical panel The wiring can enter the bottom or the back of the enclosure Knock outs provided in the base allow the wiring to be run in conduit up to the enclosure The base also has holes that line up with the mounting holes of most common electrical boxes Press down at the f...

Страница 4: ...d off red red Caution Signal wiring must be rated at least 300 V H2051A Power L 1 N 5 C1 1 6 tN4 3 C0 0 4 tN4 7 C2 2 8 tN4 9 C3 3 10 tN4 11 C4 4 12 tN4 Do not apply power RS 232 Tx Rx To RS 232 Serial Port Adapter 1 Reporting Enable Power On State Off On Description tN4 network of tekmarNet thermostats are connected to a tN4 Gateway 482 Refer to Thermostat wiring brochures for complete wiring sche...

Страница 5: ...25 2021 Watts Description A Universal Reset Module 422 and Duel Zone Manager 337 are connected to a tN4 Gateway 482 Refer to W422 and W337 wiring brochures for complete wiring schematic Electrical Application 482 E2 ...

Страница 6: ...2125 2021 Watts Electrical Application 482 E3 Description A Universal Reset Module 423 and Power Manager 345 are connected to a tN4 Gateway 482 Refer to W423 and W345 wiring brochures for complete wiring schematics ...

Страница 7: ...IOM T 482 2125 2021 Watts Description A tN2 House Control 402 is connected to a tN4 Gateway 482 Refer to the 402 Installation Operation Manual for a complete wiring schematic Electrical Application 482 E4 ...

Страница 8: ... terminal 2 Connect 115 V ac neutral N to terminal 1 Connect the ground wire to one of the ground screws provided in the wiring chamber The tN4 Gateway includes five tN4 buses tN4 Bus 0 terminals 3 and 4 tN4 Bus 1 terminals 5 and 6 tN4 Bus 2 terminals 7 and 8 tN4 Bus 3 terminals 9 and 10 tN4 Bus 4 terminals 11 and 12 Each tN4 bus consists of a tN4 terminal as well as a C terminal Polarity is impor...

Страница 9: ...is present there is a short circuit fault along the wires It is recommended to replace the tN4 bus wires 5 To test for open circuits Disconnect the tN4 bus wires on one end and connect them together Disconnect the tN4 bus wires on the other end Use an electrical meter to measure for continuity If there is no continuity there is an open circuit fault along the wires It is recommended to replace the...

Страница 10: ...er is on Power is off Tx Flashes when RS232 message is sent No RS232 message Rx Flashes when RS232 message is received No RS232 message tN4 Bus 0 tN4 communication on bus 0 b is present No tN4 communication on bus 0 tN4 Bus 1 tN4 communication on bus 1 is present No tN4 communication on bus 1 tN4 Bus 2 tN4 communication on bus 2 is present No tN4 communication on bus 2 tN4 Bus 3 tN4 communication ...

Страница 11: ...the thermostat address To determine the thermostat address please consult the data brochure for the appropriate thermostat Example 1 A thermostat with bus and thermostat device number of b 01 is wired to a model 400 controller boiler bus and in turn is wired to the 482 on port 0 This address is 0101 Example 2 A thermostat with bus and thermostat device number of b 24 is wired to a model 423 contro...

Страница 12: ...and without limiting the foregoing in any way tekmar is not responsible in contract tort or strict product liability for any other losses costs expenses inconveniences or dam ages whether direct indirect special secondary incidental or conse quential arising from ownership or use of the product or from defects in workmanship or materials including any liability for fundamental breach of contract T...

Отзывы: