8 of 12

© 2019 tekmar  304V_D - 10/19

RoomResponse

TM

 Signal

The RoomResponse

TM

 signal adjusts the temperature of a 

modulating condensing boiler that accepts a 0-10 V(dc) or 4-20 

mA signal input. It works by continually adjusting boiler water 

temperatures to the lowest possible value to meet comfort 

without wasting energy. This is done by monitoring each 

thermostat's on and off time pattern and determines the ideal 

water temperature for each zone. The control then chooses the 

highest water temperature requirement of all the thermostats 

and provides a 0-10 V (dc) or 4-20 mA signal proportional to 

the boiler operating temperature. The RoomResponse

TM

 signal 

is a DOE compliant method of controlling boiler temperature 

to building load. The RoomResponse

TM

 signal is not available 

to on/off boilers.
Benefits of the RoomResponse

TM

 signal include:

•  Increase in boiler efficiency
•  Reduction of room temperature swings

•  Reduction in expansion noises from heating pipes

Mod Max % Dial

The upper limit of the 0-10 V (dc) or 4 -20 mA signal to the 

modulating condensing boiler can be set using the Mod Max 

% Dial. This sets the upper temperature limit for the boiler.
The dial is only applicable to controls set as the Master.

Mod Max %

Max Voltage

Max mA

50

5

12

60

6

13.6

70

7

15.2

80

8

16.8

90

9

18.4

100

10

20

Expansion Terminals

Connect the five wires of the expansion bus from the master 

to the member controls.

Terminal Description
A/tN4

Away signal connecting tekmar thermostats

B

RoomResponse

TM

 signal from member controls

C

Power common

D

Demand signal. 0 Vdc = demand. 2 Vdc = no demand

E

Priority signal. 0 Vdc = priority. 2 Vdc = no priority 

FUSE 6

70 80

90

60

50

100

MOD MAX %

Mod Max % dial set to 100% in the illustration.

Setting the Max Mod % Dial

Boiler Make/Model

Required Adapter

(Supplied by boiler 

manufacturer)

0-10 V (dc) /

4-20 mA

DIP Switch

Mod Max % Dial for Boiler Design Temperature

120°F

140°F

160°F

180°F

Aerco AM series

Not required

0-10 V

50%

65%

80%

100%

Bosch Greenstar

ICM Module

0-10 V

55%

70%

80%

100%

Buderus GB142, GB162

EM10 Module

0-10 V

50%

60%

75%

90%

Burnham

®

 Alpine

*

Not required

4-20 mA

50%

70%

85%

100%

Camus

®

 Modulating Micoflame

®

Not required

0-10 V

50%

60%

70%

85%

HTP Elite

Not required

0-10 V

50%

65%

80%

90%

IBC VFC and SL series

*

Not required

0-10 V

65%

75%

85%

100%

Laars

®

 Mascot LX

Not required

0-10 V

55%

70%

85%

100%

Laars

®

 Mascot FT

Not required

0-10 V

50%

65%

80%

100%

Lochinvar

®

 Knight

Not required

0-10 V

55%

70%

85%

100%

Lochinvar

®

 FTXL

*

Not required

0-10 V

55%

70%

85%

100%

NTI Trinity Fire Tube and LX

Not required

4-20 mA

55%

65%

75%

90%

Peerless PureFire

PFA-1 Adapter

0-10 V

55%

65%

75%

90%

Raypak Xfyre, Xtherm, MVB, XPakFT

Not required

0-10 V

55%

65%

80%

90%

Riverside HeatStation

*

Not required

0-10 V

50%

65%

85%

100%

Viessmann 100-W, WB1B

OpenTherm 

Module

0-10 V

55%

70%

85%

100%

Viessmann 200-W, B2HB and 300 CU3A

Not required

0-10 V

50%

60%

70%

80%

Weil-McLain

®

 Evergreen

*

Not required

0-10 V

50%

70%

85%

100%

* Requires changes to boiler's settings

Содержание Tekmar Zone Valve Control 304V

Страница 1: ...connects up to four thermostats and operates zone valves to provide heating to a zoned hydronic heating system The 304V operates a system pump whenever a zone valve opens Zone 1 can operate either a zone valve or a circulator to provide heat to an indirect domestic hot water tank with optional priority over zones 2 through 4 The 304V includes optional exercising to prevent circulator seizure when ...

Страница 2: ...ided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read manual and all product labels BEFORE using the equipment Do not use unless you know the safe and proper operation of this equipment Keep this manual available for easy access by all users Replacement manuals are available at ...

Страница 3: ...ntrol to a different circuit from that to which the receiver is connected Cet appareil numérique de la classe B respecte toutes les exi gences du Règlement sur le matériel brouilleur du Canada Radio Frequency Interference Location Keep the control dry Avoid potential leakage onto the control Maintain relative humidity less than 90 in a non condensing environment Avoid exposure to extreme temperatu...

Страница 4: ...4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 tN4 A C R W tN4 A C R W T STAT 4 tN4 A C R W T STAT 5 tN4 A C R W T STAT 6 EXPANSION tN4 A C R W tN4 A B C D E FUSE 2 FUSE 1 END SWITCH MOTOR POWER PRIORITY SYSPUMP ROOM RESPONSE ZONE 1 70 80 90 60 50 100 MOD MAX END SWITCH MOTOR ZONE 2 END SWITCH MOTOR ZONE 3 END SWITCH MOTOR ZONE 4 END SWITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6 MASTER MEMBER...

Страница 5: ...N4 A C R W tN4 A C R W T STAT 4 tN4 A C R W T STAT 5 tN4 A C R W T STAT 6 EXPANSION tN4 A C R W tN4 A B C D E FUSE 2 FUSE 1 END SWITCH MOTOR POWER PRIORITY SYSPUMP ROOM RESPONSE ZONE 1 70 80 90 60 50 100 MOD MAX END SWITCH MOTOR ZONE 2 END SWITCH MOTOR ZONE 3 END SWITCH MOTOR ZONE 4 END SWITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6 MASTER MEMBER OFF OFF OFF T STAT1PRIORITY ON EXERCISING ON POSTPURGE...

Страница 6: ...ITCH MOTOR ZONE 5 END SWITCH MOTOR ZONE 6 MASTER MEMBER OFF OFF OFF T STAT1PRIORITY ON EXERCISING ON POSTPURGE ON MODBOILER 0 10V SYSTEMPUMPDURINGPRIORITY ON SYSTEMPUMPWITHMEMBERCALL ON ZONEVALVEENDSWITCHES ON RESERVED 120 VAC POWER PUMP PUMP 1 SYSTEM PRIORITY L N L N L N OFF OFF OFF 4 20mA B1 PS L L N N P1 V1 V2 V3 V3 V4 V5 V6 A1 T1 T4 T5 T6 T7 T2 T3 N L N Power L N B1 P1 A1 Expansion PS V2 V1 V3...

Страница 7: ...nstalled and the Zone Valve End Switches DIP switch is set on Exercising DIP Switch ON Each circulator pump is energized for 30 seconds every 72 hours OFF Circulator pump exercising disabled Post Purge DIP Switch ON After thermostat 1 stops calling for heat the zone 1 priority pump and zone valve remain on for 2 minutes to purge heat from the boiler to the zone OFF Post purge disabled Mod Boiler D...

Страница 8: ...pansion bus from the master to the member controls Terminal Description A tN4 Away signal connecting tekmar thermostats B RoomResponseTM signal from member controls C Power common D Demandsignal 0Vdc demand 2Vdc nodemand E Priority signal 0 Vdc priority 2 Vdc no priority FUSE 6 70 80 90 60 50 100 MOD MAX Mod Max dial set to 100 in the illustration Setting the Max Mod Dial Boiler Make Model Require...

Страница 9: ...tpoint Source Change Energy Management setting Central Heat Modulation Source to 4 20 mA Change Energy Management setting Central Heat 4 20 mA Setup 4 mA Water Temperature to 80 F 26 5 C 9 10 22 23 5 6 16 17 2 U 1 X X T T 1 2 9 10 No changes to the boiler are required Aerco AM Series Bosch Greenstar Buderus GB142 and GB162 Burnham Alpine Camus Modulating MicoFlame Heat Transfer Products Elite IBC ...

Страница 10: ...ameter to ACTIVE Set BMS Type to SETPOINT Enter boiler password Set Parameter Setpoint source to 4 20mA Enter boiler password Set Parameter Setpoint source to 4 20mA Lochinvar Knight Lochinvar FTXL NTI Trinity LX Riverside HeatStation NTI Trinity Fire Tube 304V 304V 304V 304V 304V Sensor I O 24Vac I O X X W R 1 2 37 38 X X W R 21 22 35 36 X X CH1 R 3 5 11 12 X X CH1 R 3 5 4 5 8 EMS 9 Laars Mascot ...

Страница 11: ...y 2 Volts For Min to 2 V Set Local Priority 2 Volts For Max to 10 V Install the OpenTherm Module as per the boiler manufac turer s instructions Raypak MVB or XTherm Raypak XFyre or XPakFT 304V 304V J2 J1 X X 13 14 17 18 X X T T 8 9 9 10 Viessmann OpenTherm Module Viessmann Extension Module EA1 Plug 0 10V Weil McLain Evergreen P15 304V 304V 304V 1 4 1 2 5 6 Connect to the Viessmann Extension Module...

Страница 12: ...ar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to any such representations or war ranties by Purchaser to its customers The pass through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar accident fire Act of God abuse or misuse or has been damaged by mo...

Отзывы: