background image

8

The following tests are to be performed using standard testing practices and procedures
and should only be carried out by properly trained and experienced persons.

A good quality electrical test meter, capable of reading from at least 0 — 200 V (ac) and at
least 0 — 2,000,000 Ohms, is essential to properly test the wiring and sensors.

Test the Sensors

 

In order to test the sensors and Room Temperature Units (RTUs), the actual temperature
at each sensor and RTU location must be measured. A good quality digital thermometer
with a surface temperature probe is recommended for ease of use and accuracy of
testing. Where a digital thermometer is not available, a spare sensor can be strapped
alongside the one to be tested and the readings compared. Test the sensors and RTU(s)
according to the instructions in the Data Brochures D 070, D 074 and D 054.

Test the Power Supply

 

Make sure exposed wires or bare terminals are not in contact with other wires or grounded surfaces. Turn on the power and measure
the voltage between the 

Power N — L (3 and 4) terminals using an AC voltmeter. The reading should be between 110 and 130 V (ac).

Test the Outputs

 

System Pump

If a system pump is connected to the 

System Pmp — System Pmp (1 and 2) terminals, make sure power to the terminal block is

off and install a jumper between the terminals. When the system pump circuit is powered up, the system pump should start. If the
pump does not turn on, check the wiring between the terminal block and the pump and refer to any installation or troubleshooting
information supplied with the pump. If the pump operates properly, disconnect the power and remove the jumper.

Zone Pump or Valve

• If a zone pump or valve is connected to the terminals 

Com 1-2 —1 (15 and 16), make sure power to the pump or valve circuit is

off and install a jumper between the terminals 

Com 1-2 —1 (15 and 16). When the zone circuit is powered up, the zone pump

should turn on or the zone valve should open completely. If this does not occur, check the wiring between the terminal and the
pump or valve and refer to any installation or troubleshooting information supplied by the manufacturer.

• If a zone pump or valve is connected to the terminals

 Com 1-2 — 2 (15 and 17), follow a similar procedure as described above

for the zone 1 relay.

• If a zone pump or valve is connected to the terminals 

Com 3-4 — 3 (18 and 19), follow a similar procedure as described above

for the zone 1 relay.

• If a zone pump or valve is connected to the terminals 

Com 3-4 — 4 (18 and 20), follow a similar procedure as described above

for the zone 1 relay.

Connect the Control

  

• Make sure all power to the devices and terminal blocks is turned off and remove any remaining jumpers from the terminals.

• Reconnect the terminal blocks to the control by carefully aligning them with their respective headers on the control and then pushing

the terminal blocks into the headers. The terminal blocks should snap firmly into place.

• Install the supplied safety dividers between the unpowered sensor inputs and the powered 120 V (ac) or 24V (ac) wiring chambers.

• Do not apply power to the control until the adjustment dials and DIP switches are properly set for your application. See the  Settings

section of this brochure for details on how to set the dials and DIP switches.

• Once the settings are complete, apply power to the control. The operation of the control on power up is described in the Sequence

of Operation section of this brochure.

 

Settings

Before adjusting the dial settings, read through the sequence of operation section of this brochure to ensure that you understand how
the control operates.

STEP SIX 

 ESSENTIAL CONTROL SETTINGS 

UnOccupied

The

 UnOccupied dial is used to set the desired temperature in selected zones during the

UnOccupied period.

Using the Internal 24 hr. Timer

 

First determine the length of time required for the UnOccupied period and turn the
UnOccupied Duration dial to the desired duration length. If the dial is set to 24 hours, the
368 remains in UnOccupied mode continuously. If the dial is set to 0 hours, the 368
remains in Occupied mode continuously.

8

9

10

12

11

13 14

Zo

Out

RTU

4

Zo
In

Com
Sen

RTU

3

UnO

Sw

Com
Sen

UnOccupied

Duration

Timer Active

24 hr. Timer

• Dial the desired duration of the
UnOccupied period.
• Press start button at the time of day
you want the UnOcc. period to begin.
Timer Active light turns on.

Start

0 = always Occupied
24 = always UnOccupied

0

12 hrs.

24

6

18

UnOccupied

Duration

Содержание Tekmar Zone Control 368

Страница 1: ...8 70 F 21 C 40 4 100 38 UnOccupied 5 6 7 LR 58223 NR T L C R Occupied Optimum Start Stop UnOccupied Timer Active 24 hr Timer 0 12 hrs 24 6 18 Dial the desired duration of the UnOccupied period Press s...

Страница 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Страница 3: ...ulationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and outdoor sensors are used Optimum Start Stop...

Страница 4: ...relay is then turned on and its on time is increased as the load increases When the heating load decreases again the on time of the Hi stage relay is reduced until the Hi stage relay is turned off co...

Страница 5: ...cupied mode the UnOccupied light is turned on and the UnOccupied dial is used to set the desired temperature within the UnOccupied zones Note If the RTU dial for an UnOccupied zone is set below the Un...

Страница 6: ...ng hardware and conduit fittings Before removing the knockouts check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections...

Страница 7: ...RTU 3 and RTU 4 If the common block is used for a Two Stage heating zone connect the RTU or Indoor Sensor to terminals Com Sen RTU 4 8 and 10 Output Connections System Pump Connect the live L side of...

Страница 8: ...plied by the manufacturer If a zone pump or valve is connected to the terminals Com 1 2 2 15 and 17 follow a similar procedure as described above for the zone 1 relay If a zone pump or valve is connec...

Страница 9: ...ic motor zone valves or zone pumps are used the DIP switch must be set to Off Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 368 has a test routine whi...

Страница 10: ...g system is turned off during the final stages of the Occupied period Timer Active The timer is set to enter the UnOccupied mode every 24 hours at the time of day the Start button was pressed STEP EIG...

Страница 11: ...m Start Stop UnOccupied Timer Active Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 Temperature sensor open Power Heat Required Occupied Optimum Start Stop UnOccupied Ti...

Страница 12: ...cable environmental health or safety legislation No implied warranties shall extend beyond twenty four 24 months from the production date Some states or provinces do not allow limitations on how long...

Отзывы: