![Watts Tekmar WiFi Snow Melting Control 670 Скачать руководство пользователя страница 28](http://html2.mh-extra.com/html/watts/tekmar-wifi-snow-melting-control-670/tekmar-wifi-snow-melting-control-670_installation-manual_3765323028.webp)
28 of 48
tekmarNet Menu
Description
Range
Access
ADDRESSING
The tekmarNet address of this control. Select between automatic and manual addressing.
To manually set the address, use the up or down buttons.
Conditions: Available when the 670 is connected to other controls using tekmarNet communication.
Auto,
b:01 to b:24,
1:01 to 1:24,
2:01 to 2:24,
3:01 to 3:24
Installer
DEVICE COUNT
Provides a count of all the tekmarNet thermostats, setpoint controls and snow melting controls
on a tN4 bus.
Conditions: Available when the 670 is connected to other controls using tekmarNet communication.
1 to 24
Installer
SNOW MELT ZONE
Select the snow melting zone that this control operates. Snow zone 1 has the highest priority
while snow zone 12 has the lowest priority.
Conditions: Available when the 670 is connected to other controls using tekmarNet communication.
1 to 12
Installer
TRACK ZONE
Select to track and record the running hours of snow zone 1 and repeat this run time on this
control. This allows snow melting zones without a snow/ice sensor to automatically start.
Conditions: Available when 1) The 670 is connected to other controls using tekmarNet communication
and 2) Snow zone is set to 2 through 12.
Off or On
Installer
MELT GROUP
A User Switch or Gateway may be used to manually start melting the zone. Set the Melt
Group number to the corresponding Setpoint Enable number on the User Switch or Gateway.
Conditions: Available when the 670 is connected to other controls using tekmarNet communication.
1 to 12
Installer
STORM GROUP
A User Switch or Gateway may be used to manually start the storm operation for the zone.
Set the Storm Group number to the corresponding Setpoint Enable number on the User
Switch or Gateway.
Conditions: Available when the 670 is connected to other controls using tekmarNet communication.
1 to 12
Installer
PRIORITY
Select the priority of the snow melting system.
Conditions: Available when 1) The 670 is connected to other controls using tekmarNet communication
and 2) Application Mode is set to PWM Mode, Mix or Electric.
Off, Conditional,
Full
Default = Off
Installer
AWAY SCENE
Select if the control should accept or ignore the away command from the mobile app or
from a tekmarNet system.
Conditions: Always available.
Off or On
Default = On
Installer
TN4 SYSTEM PUMP
Select if the system pump located on the tekmarNet System Control should operate when
the snow melt zone is heating.
Conditions: Available when the 670 is connected to other controls using tekmarNet communication.
Off or On
Installer