24 of 36
Setting
Range
Default
HEATING TYPE
Select between conventional heating or heat pump.
Conventional,
Heat Pump
Conventional
EQUIPMENT
Select the number of stages of the heating and
cooling equipment.
Conventional
1 Heat/1 Cool,
1 Heat/2 Cool,
2 Heat/1 Cool,
2 Heat/2 Cool,
1 Heat/
1 Cool
Heat Pump
1 HP,
1 HP/1 Aux,
1 HP/2 Aux,
2 HP,
2 HP/1 Aux,
2 HP/2 Aux
1 HP/1 Aux
RADIANT FLOOR HEATING
Select if the first stage W1 heats a radiant floor.
Yes or No
No
HEAT 2 DIFFERENTIAL
Select when the second stage heating turns on. Turn
on point is the Heat To setting minus the differential.
2.0 to 10.0°F
1.0 to 5.6°C
2.0°F
1.2°C
HEAT 2 DELAY
Select the time delay when the second stage heating
turns on. The time delay starts counting after the first
stage heating is turned on. This setting is available
when there are at least 2 heating stages.
0 to 180
minutes
1 minute
HEAT 3 DIFFERENTIAL
Select when the third stage heating turns on. Turn
on point is the Heat To setting minus the differential.
This setting is available when a heat pump is
selected and there are at least 3 heating stages.
2.0 to 10.0°F
1.0 to 5.6°C
2.5°F
1.4°C
HEAT 3 DELAY
Select the time delay when the third stage heating
turns on. The time delay starts counting after the
second stage heating is turned on. This setting is
available when a heat pump is selected and there
are at least 3 heating stages.
0 to 180
minutes
1 minute
HEAT 4 DIFFERENTIAL
Select when the fourth stage heating turns on. Turn
on point is the Heat To setting minus the differential.
This setting is available when a heat pump is
selected and there are 4 heating stages.
2.0 to 10.0°F
1.0 to 5.6°C
3.0°F
1.8°C
Setup - Relays (1 of 3)
------------------------------------------------
------------------------------------------------