24
Notifications Menu
The control keeps track of the last 30 errors and alert
notifications .
Refer to the Troubleshooting section for corrective action .
Overrides Menu
Parameter
Range
Description
OPERATION
Automatic, Hand,
Purge, Max Heat, Off
Set the manual override .
Automatic reverts to normal operation .
Hand allows each output to be turned on or set manually .
Max Heat operates the heating system at the boiler maximum setting .
Off places the control into a standby state and the boilers and pumps are not operated .
COMBUSTION AIR
DAMPER
Off or On
Default: Off
Select to turn on the combustion air damper . Available in Hand override .
BOILER 1 ENABLE
Off or On
Default: Off
Set on to fire the boiler . Available in Hand override when Boiler 1 Enable is on .
Available in Hand override .
BOILER 2 ENABLE
Off or On
Default: Off
Set on to fire the boiler . Available in Hand override when Boiler 2 Enable is on .
Available in Hand override .
BOILER MAX HEAT
PERCENTAGE
5% to 100%
Default: 100%
Select the boiler run time percentage of the heating cycle . Available when set to
Max Heat Override .