The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, 
this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equip-
ment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the 
control off and on, the user is encouraged to try to correct the interference by reorienting or relocating the receiving antenna, relocating the 
receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Caution

 The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bushings and jumper wires.

Attention

 Un boîtier nonmétallique n’assure pas la continuité électrique des conduits. Utiliser des manchons ou des fils de accord spécialement 

conçus pour la mise á la terre.

Technical Data

Limited Warranty and Product Return Procedure

Boiler Control 256 

One Stage Boiler

Literature

D256, A256

Control

Microprocessor control. This is not a safety (limit) control

Packaged weight

1.3 lb. (580 g)

Dimensions

4-3/4" H x 2-7/8" W x 7/8" D (120 x 74 x 22 mm)

Enclosure

White PVC plastic, Nema Type 1

Approvals

CSA C US, meets class B: ICES & FCC Part 15

Ambient conditions

Indoor use only, 32 to 104°F (0 to 40°C), RH ≤90% Non-condensing

Power supply

24 V ±10%, 50/60 Hz, 3 VA, Class 2

Relay

240 V (ac) 5 A 1/6 hp

Demand

24 V (ac) 2 VA

Sensors

NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892

–Included

Outdoor Sensor 070 and Universal Sensor 071

–Optional

tekmar type #: 033

Warranty

Limited 3 Year

WARNING:

 This product contains chemicals known to the State of 

California to cause cancer and birth defects or other reproductive harm.  

For more information: Watts.com/prop65

256_D - 09/19

 

20 of 20 

© 2019 tekmar

Tel: (250) 545-7749 • Fax: (250) 984-0815

 tekmarControls.com

All specifications are subject to change without notice

Limited Warranty 

The liability of tekmar under this warranty is limited. The 

Purchaser,  by  taking  receipt  of  any  tekmar  product  (“Product”),  acknowl-

edges the terms of the Limited Warranty in effect at the time of such Product 

sale and acknowledges that it has read and understands same.

The tekmar Limited Warranty to the Purchaser on the Products sold hereunder 

is a manufacturer’s pass-through warranty which the Purchaser is authorized to 

pass through to its customers. Under the Limited Warranty, each tekmar Prod-

uct is warranted against defects in workmanship and materials if the Product 

is installed and used in compliance with tekmar’s instructions, ordinary wear 

and  tear  excepted.  The  pass-through  warranty  period  is  for  a  period  of  twen-

ty-four (24) months from the production date if the Product is not installed during 

that period, or twelve (12) months from the documented date of installation if 

installed within twenty-four (24) months from the production date.

The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s 

sole discretion: the cost of parts and labor provided by tekmar to repair defects in 

materials and / or workmanship of the defective product; or to the exchange of the 

defective product for a warranty replacement product; or to the granting of credit 

limited to the original cost of the defective product, and such repair, exchange or 

credit  shall  be  the  sole  remedy  available  from  tekmar,  and,  without  limiting  the 

foregoing  in  any  way,  tekmar  is  not  responsible,  in  contract,  tort  or  strict  prod-

uct liability, for any other losses, costs, expenses, inconveniences, or damages, 

whether  direct,  indirect,  special,  secondary,  incidental  or  consequential,  arising 

from ownership or use of the product, or from defects in workmanship or materials, 

including any liability for fundamental breach of contract.

The  pass-through  Limited  Warranty  applies  only  to  those  defective  Products 

returned  to  tekmar  during  the  warranty  period.  This  Limited  Warranty  does  not 

cover the cost of the parts or labor to remove or transport the defective Product, or 

to reinstall the repaired or replacement Product, all such costs and expenses being 

subject to Purchaser’s agreement and warranty with its customers.

Any representations or warranties about the Products made by Purchaser to its cus-

tomers which are different from or in excess of the tekmar Limited Warranty are the 

Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold 

tekmar harmless from and against any and all claims, liabilities and damages of any 

kind or nature which arise out of or are related to any such representations or war-

ranties by Purchaser to its customers.

The pass-through Limited Warranty does not apply if the returned Product has been 

damaged by negligence by persons other than tekmar, accident, fire, Act of God, 

abuse or misuse; or has been damaged by modifications, alterations or attachments 

made subsequent to purchase which have not been authorized by tekmar; or if the 

Product was not installed in compliance with tekmar’s instructions and / or the local 

codes and ordinances; or if due to defective installation of the Product; or if the Prod-

uct was not used in compliance with tekmar’s instructions.

THIS  WARRANTY  IS  IN  LIEU  OF  ALL  OTHER  WARRANTIES,  EXPRESS  OR 

IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTU-

ALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF 

MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY 

OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY REL-

EVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VI-

OLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEG-

ISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRAC-

TUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND 

TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT 

THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW. 

Product  Warranty  Return  Procedure

  All  Products  that  are  believed  to  have 

defects  in  workmanship  or  materials  must  be  returned,  together  with  a  written 

description of the defect, to the tekmar Representative assigned to the territory in 

which such Product is located. If tekmar receives an inquiry from someone other 

than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar 

Representative) or Purchaser’s customers, regarding a potential warranty claim, 

tekmar’s sole obligation shall be to provide the address and other contact informa-

tion regarding the appropriate Representative.

BOIL

F

OCC

Press & Release:

all 3 buttons, to adjust menu

Press & Hold:

Item

, to view settings

 , to test.

Boiler Control 256

One Stage Boiler

Item

Date Cod

e

Power:  24 V ±10% 50/60 Hz

 

3 VA Class 2

Relay:  240 V (ac) 5 A 1/6 hp

Meets Class B:

Canadian ICES

FCC Part 15

H1

19

0D

Terminal Unit

Boiler Demand

Inst / A

dv

1

Boil

2

Out

3

Com

4

UnO

Sw

5

Boiler

6 7

T

8

Power

R+

9

C-

Do not apply power

tektra 909-01

Designed & 

Assembled in 

Canada 

Signal wiring 

must be rated 

at least 300V

Содержание Tekmar 256

Страница 1: ... Input 24 V ac Power Supply Output Boiler Input tekmar Timer Optional BOIL F OCC Input Boiler Demand Signal PRGM S TIME AMPM UNOCC OVR S M W T F T 1 2 Press Release all 3 buttons to adjust menu Press Hold Item to view settings to test Boiler Control 256 One Stage Boiler Item Date Code Power 24 V 10 50 60 Hz 3 VA Class 2 Relay 240 V ac 5 A 1 6 hp Meets Class B Canadian ICES FCC Part 15 H1190D Termi...

Страница 2: ...yed in the item field of the display To view the next available item press and release the Item button Once you have reached the last available item pressing and releasing the Item button will return the display to the first item Adjust To make an adjustment to a setting in the control press and hold simultaneously for 1 second all 3 buttons The display will then show the word ADJUST in the top ri...

Страница 3: ... the selected item Terminal Unit TARGET INDR DSGN DIFF BOIL OUTDR ROOM WWSD F C MAX MIN OCC UN VIEW ADJUST Boiler Demand Burner Displays when the boiler relay is turned on F C F C Displays the unit of measure that all of the temperatures are to be displayed in the control OCC Occupied Schedule Displays when the control is in occupied Day mode UNOCC Unoccupied Schedule Displays when the control is ...

Страница 4: ...rted together the control operates in the unoccupied Night mode When in the unoccupied Night mode the UNOCC segment is displayed in the LCD The 256 adjusts the supply water temperature based on the UNOCC settings made in the control FACTORY DEFAULTS The control comes preset with several factory defaults These defaults are based on the terminal unit selection see section B2 To fine tune building re...

Страница 5: ...l unit is used the control varies the supply water temperature according to the type of terminal unit This improves the control of the air temperature in the building BOILER TARGET TEMPERATURE BOIL TARGET The BOIL TARGET temperature is determined from the Characterized Heating Curve settings and the outdoor air temperature The control displays the temperature that it is currently trying to maintai...

Страница 6: ...r a thick concrete or gypsum pour This heating system has a large thermal mass and is slow acting Default values BOIL DSGN 120 F 49 C BOIL MIN OFF Low Mass Radiant 2 This type of radiant heating system is either attached to the bottom of a wood sub floor suspended in the joist space or sandwiched between the sub floor and the surface This type of radiant system has a relatively low thermal mass an...

Страница 7: ...he BOIL TARGET temperature The boiler maximum is the BOIL DSGN plus 10 F 5 C but limited to 225 F 107 C If the control does target the boiler maximum and the BOIL temperature is near the boiler maximum temperature the MAX segment will be displayed in the LCD while either the BOIL TARGET temperature or the BOIL temperature is being viewed At no time does the control operate the boiler above 248 F 1...

Страница 8: ...ever the control does not operate the heating system to satisfy this demand CAUTION Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards This electronic control is not intended for use as a primary limit c...

Страница 9: ...it snaps into place STEP TWO CONTROL INSTALLATION STEP THREE SENSOR INSTALLATION Caution Do not run sensor wires parallel to telephone or power cables If the sensor wires are located in an area with strong sources of electromagnetic interference shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit If using shielded cable the shield wire should be connec...

Страница 10: ...resents the heat load on the building a northern wall for most buildings The 070 should not be exposed to heat sources such as ventilation or window openings The 070 should be installed at an elevation above the ground that will prevent accidental damage or tampering Connect 18 AWG or similar wire to the two terminals provided in the enclosure run the wires from the sensor to the control Do not ru...

Страница 11: ... steel black iron pipe is used In general it is recommended that a temperature well be used for steel pipe of diameter greater than 1 1 4 32 mm Temperature wells are also recommended when large diameter pipes are used and fluid stratification is present Conduit Connection The Universal Sensor and Universal Sensor Enclosure 080 sold separately are specifically designed to mount onto a 3 8 10 mm ID ...

Страница 12: ...80 50 10 19 900 120 49 3 760 190 88 983 15 26 139 403 55 13 17 436 125 52 3 383 195 91 903 10 23 118 018 60 16 15 311 130 54 3 050 200 93 829 5 21 100 221 65 18 13 474 135 57 2 754 205 96 763 0 18 85 362 70 21 11 883 140 60 2 490 210 99 703 5 15 72 918 75 24 10 501 145 63 2 255 215 102 648 10 12 62 465 80 27 9 299 150 66 2 045 220 104 598 15 9 53 658 85 29 8 250 155 68 1 857 225 107 553 A good qua...

Страница 13: ...etween 21 and 27 V ac when the boiler demand device calls for heat Test The Outputs Boiler Make sure power to the boiler circuit is off and short the boiler wires When the boiler circuit is powered up the boiler should fire If the boiler does not turn on refer to any installation or troubleshooting information supplied with the boiler The boiler may have a flow switch that prevents firing until th...

Страница 14: ...d Input Connections Do not apply power to these terminals as this will damage the control Outdoor Sensor Connect the two wires from the Outdoor Sensor to the Out and Com terminals 2 and 3 The outdoor sensor is used by the 256 to measure the outdoor air temperature Universal Sensor Connect the two wires from the Universal Sensor to the Boil and Com terminals 1 and 3 This sensor is used by the 256 t...

Страница 15: ...n to set the desired temperature The ROOM UNOCC setting is set to the desired room air temperature during the unoccupied Night mode Note To increase or decrease space temperature during the unoccupied Night mode only adjust the ROOM UNOCC setting This is only used if a tekmar timer is installed Press and release the Item button to advance to the OUTDR DSGN adjustment Use the or button to set the o...

Страница 16: ...outdoor air temperature used in the heat loss calculation for the heating system 60 to 32 F 51 to 0 C B2 The type of terminal units that are being used in the heating system B2 S e c t i o n A d v a n c e d I n s t a l l e r Display Description Range Actual Setting The design indoor air temperature used in the heat loss calculation for the heating system 35 to 100 F 2 to 38 C B3 The design supply ...

Страница 17: ...F OFF B3 The system s warm weather shut down during the unoccupied Night period 35 to 100 F OFF 2 to 38 C OFF The units of measure that all of the temperatures are to be displayed in the control F C This item exits the ADJUST menu by pressing either the or button S e c t i o n A d v a n c e d I n s t a l l e r Display Description Range Actual Setting B3 Adjust Menu 2 of 2 2019 tekmar 256_D 09 19 1...

Страница 18: ...hours of time in troubleshooting a system Note flow directions in the system paying close attention to the location of pumps check valves pressure bypass valves and mixing valves Ensure correct flow direction on all pumps This is also a very useful step if additional assistance is required Document the control for future reference Before making any adjustments to the control note down all of the i...

Страница 19: ...act will operate for up to 10 minutes of a 20 minute cycle Locate and repair the problem as described in the Testing section To clear the error message from the control after the sensor has been repaired press the Item button The control is no longer able to read the boiler sensor due to an open circuit In this case if the BOIL MIN adjustment is set to OFF the control does not operate the Boiler c...

Страница 20: ... original cost of the defective product and such repair exchange or credit shall be the sole remedy available from tekmar and without limiting the foregoing in any way tekmar is not responsible in contract tort or strict prod uct liability for any other losses costs expenses inconveniences or damages whether direct indirect special secondary incidental or consequential arising from ownership or us...