11
The
Water Hardness
level of the feed water needs to be known before programming the system, as well as the
Water Softener Capacity
of
the system being installed, to assure proper programming and efficiency of the system.
Chart 1: Setting Time of Day
Press
Set Clock
Adjust hours using the
UP
and
DOWN
arrows.
Press
NEXT
to advance to the minutes Adjust minutes with the
UP
and
DOWN
arrows.
Press
NEXT
to set time
Setting Time of Day completed.
Once in the programming settings, use the
UP
and
DOWN
arrows to change values.
Chart 2: Master Programming
To enter the Master Programming
mode, press and hold the
NEXT
and
DOWN
arrows simultaneously
for 3 to 5 seconds
The display changes to
SET SOFTENING
with the word
SOFTENING
blinking. This indicates
you are now in the Master Programming Mode.
System Type – For a
WATER SOFTENER
, leave this setting alone. If for some reason the dis-
play reads
SET FILTER
, press the
UP
arrow and change to
SET
SOFTENER.
Press
NEXT
Capacity – Enter the
CAPACITY
of the water softener that you have; that is,
30K, 45K, 60K or
90K.
Press
NEXT
Salt Setting – Enter the desired pounds of salt per regeneration. Example: 6 lb/cu ft of resin for
highest efficiency; 15 lb/cu ft for maximum capacity. Default setting should be
9
pounds for a 45K
water softener. Confirm the setting.
Press
NEXT
A 30K water softener has 1 cu ft, 45K has 1.5 cu ft, 60K has 2 cu ft, and 90K cu ft has 3 cu ft.
Example: 45K water softener would be set to a minimum salt setting of 9 pounds for highest effi-
ciency (recommended).
Press
NEXT
Backwashing Mode - Setting to Normal or Longer.
NORMAL
is the standard setting.
LONGER
may be needed for well water with heavier sediment issues. Contact Pure Water Technical
Support at
1.800.224.1299, then press #2
for details.
Press
NEXT
Gallon Capacity Mode - Set to
AUTO
for most efficient setting. Owner’s manual has additional
settings. Contact Pure Water Technical Support for details. Note: You may see a gallon capacity
on this screen, press the
UP
arrow several times until you see
AUTO
on the screen.
Press
NEXT
Brine Tank Refill Mode - Set to
POST.
Press
NEXT
Regenerate Flow Mode - Set to Down Flow –
dn.
Press
NEXT
Regeneration Time - Set to
NORMAL.
Press
NEXT
Master Programming completed.
Next you need to set up Installer Programming, this
MUST
be done in addition to the Master Programming.
Chart 3: Installer Programming
To enter Installation Display Setting
Programming mode, press and hold
the
NEXT
and
UP
arrow buttons
simultaneously for 3 to 5 seconds
Hardness Setting - Set the level of hardness in grains per gallon (GPG) present in the raw water.
Example:
18
grains per gallon (GPG). Adjust grains per gallon with the
UP
and
DOWN
arrows.
Press
NEXT
Day Override. Default should be set to
14
Days. Watts Pure Water water softeners regenerate
based on water usage, but this day override setting comes into play if the softener sits idle or has
not regenerated. It initiates regeneration automatically regeneration on the 14th day.
Press
NEXT
Regeneration Time. Default setting is
2:00 AM
. If time change is needed, press the
UP
and
DOWN
arrows to adjust the hour time.
Press
NEXT
Press the
UP
and
DOWN
arrows to adjust the minutes.
Press
NEXT
Installer Programming completed. Valve returns to normal mode and is in service.
If you have additional questions regarding your water softener programming, contact