CENTURION Installation, Operation & Maintenance Manual
SECTION 2: INSTALLATION
On all Centurion models it is strongly recommended that the pressure regulator be installed a
minimum distance of 10 pipe diameters between the pressure regulator and the nearest
downstream
fittings (an elbow or the unit itself), and a minimum of 5 pipe diameters between the
pressure regulator and any
upstream
fitting, such as elbow or shutoff valve, as shown below.
Figure 2-11: Gas Regulator and Manual Shut-Off Valve
2.8.3 Massachusetts Installations Only
For Massachusetts installations, a mandatory external gas supply regulator must be positioned
as shown in Figure 2-11. The gas supply regulator must be properly vented outdoors.
2.8.4 Manual Gas Shutoff Valve
A manual shut-off valve must be installed in the gas line upstream from the unit, as shown.
2.9 AC Electrical Power Wiring
Centurion Water Heaters CEN 2000/1600 are available with the following power options:
Voltage
Phase
Amperage
208 V
3
/
60 Hz
20
460 V
3
/
60 Hz
15
2.9.1 Power Panel Locations
External AC power connection is made inside the Power Panel, located on the front of the unit,
behind the unit’s removable front panel.
Figure 2-12: Power Panel
GAS INLET
GAS PRESSURE
REGULATOR
MANUAL SHUT-
OFF VALVE
GAS INLET
MAIN POWER PANEL
SECONDARY
POWER PANE
I/O BOARD
(Protector in place)
MINIMUM 10 PIPE
DIAMETERS IN LENGTH
MINIMUM 5 PIPE
DIAMETERS IN LENGTH