2
!
Notice to Installer
• Do not discard this manual after installation. This manual
contains important operation, maintenance and precaution-
ary information. Please present this manual to user/operator/
owner after installation.
• It is strongly encouraged that you read this manual before
installing the system to ensure the best possible installation.
• Installation must conform to all local and state plumbing codes
and regulations.
• Connect system to cold water supply only. Water temperature
cannot exceed 100°F/28°C.
• System
must be
installed in a vertical, upright and level
position.
• OneFlow
®
systems
must not
be used in conjunction with
polyphosphate or any other scale inhibitor.
• Do not use with water that is microbiologically unsafe or of
unknown quality without adequate disinfection before or after
the system.
• Notice to user/operator/owner: Please retain this manual for
future reference for parts, maintenance or troubleshooting.
• It is recommended that all personnel responsible for operation
and maintenance of this product read the precautions, operation
and maintenance sections of this manual.
Installation Precautions!
• Do
NOT
install system on line pressure above 125psi.
• Do
NOT
install system on HOT water line. Failure to limit line
temperature to 100°F may result in housing failure and damage.
• Do
NOT
install the system backwards with the feed water line
connected to the outlet.
• Do
NOT
use liquid pipe compounds for fitting connections.
USE two to three wraps of Teflon
®
tape.
• Do
NOT
solder plumbing connections attached to filter housing
or inlet valve. Inlet valve and filter housing will be damaged by
high temperature.
• Do
NOT
allow system to freeze. Turn off water supply to housing
and drain housing if temperature falls below 32°F.
• Do
NOT
install system in direct sunlight or where system is
exposed to harsh chemicals or may be subjected to being
struck by moving equipment, carts, mops or any other item
that may cause damage.
•
ALLOW
a minimum of 3” under the housing to allow for filter
replacement.
•
IF
water hammer is evident, install water hammer arrestors
before the OneFlow
®
unit.
• Do
NOT
overtighten fitting connections into inlet valve or
housing outlet.
• Always back-up valves and fittings with a wrench when
installing a fitting to avoid turning the valve.
• Do
NOT
install the unit behind equipment where it may be
difficult to access the system for filter replacement.
Position the OneFlow
®
unit in a suitable location. The direction of flow
through the OneFlow
®
unit is always left to right; keep this in mind
when determining installation location. Do NOT mount the OneFlow
®
system near any source of heat. Also, do not mount the system above
any device or area that would be adversely effected by water.
Installation
1. Turn off all equipment to be fed by the OneFlow
®
System,
locate water supply shutoff valve and turn OFF
2. Determine if the water line has an existing water treatment
system. If so, examine system for use of polyphosphate or
other scale inhibitors. OneFlow
®
will not be effective if used
in conjunction with other scale inhibitors. Remove the scale
inhibitors from the water line or discontinue installation.
3. Install a
1
/
2
” full-flow ball valve on the water supply side that
will feed the water system.
4. Anchor the OneFlow
®
system on a wall stud or suitable
mounting material spanning wall studs. System must be verti-
cal and upright.
5. Run a suitable line from the
1
/
2
” full-flow ball valve at the tap
water source to the inlet ball valve on the left side of the
OneFlow
®
system. Use 2-3 wraps of Teflon
®
tape and brace
the inlet ball valve on the system with a wrench when con-
necting the feed water line.
NOTE:
DO NOT OVERTIGHTEN
CONNECTION FITTING INTO BALL VALVE.
6. Select the appropriate size tubing for the equipment being fed
and connect it to the outlet of the OneFlow
®
System.
NOTE:
DO NOT connect the tubing to the equipment at this time. Prior
to making connection to the equipment, this line will be used to
facilitate flushing the system. As an option, a drain valve in a tee
on the outlet side of the OneFlow
®
system could be provided in
the line to facilitate flushing when changing filters.
7. With OneFlow
®
inlet valve closed, slowly open the
1
/
2
” full-
flow ball valve at the tap water source. Check for leaks.
8. If a drain valve was not installed on the outlet side of the system,
hold the tubing that will connect to equipment in a clean bucket
or over sink or drain. Open the system inlet feed valve and allow
water to flush through system for 2 minutes at the specified
system flow rate to allow air bubbles to escape.
NOTE:
NO
ACTIVATION IS REQUIRED FOR THE OneFlow
®
SYSTEM TO
PERFORM PROPERLY. FLUSHING IS RECOMMENDED TO
ALLOW AIR TO ESCAPE THE SYSTEM.
9. Make certain that the end of the tubing to be connected to
the equipment is clean and sanitary.
10. Connect tubing to equipment. Open all water supply valves
and check for leaks.
11. If no leaks, turn on equipment and check for normal operation.
12. Attach the Service Log to the installed OneFlow
®
System and
fill in install date.
i
!
2
Teflon
®
is a registered trademark of the E.I. Dupont de Nemours & Company.
Содержание OneFlow OF140-4