background image

Flow curves are for reference. Actual flows may vary depending on system 

temperatures and/or pressures. 

*Flow curve with integral inlet filters and check valves

Capacity*

 

kpa  psi 

 

345  50

 276  40

 207  30

 138  20

  69  10

0

 8 

10 

12 

14 

gpm 

 

7.6 

15 

23 

 30 

38 

46 

53 

lpm

Pressure 

Drop

Flow

Watts MMV-M1 and LFMMV-M1 Troubleshooting Guide

Problem & Cause

 A. Unable to reach required set point or set point difficult to set
 

A.1  Supply temperatures not within specified limits 

 

A.2  Hot and cold supplies reversed

 

A.3  Filters are blocked by debris 

B. Unable to achieve required flow
 

B.1  Too much pressure drop at fixture  

 

B.2  Checks valve/filters blocked by debris

 C.  Valve does not maintain required temperature or temperature 

changes over time

 

C.1  Fluctuation in supply pressures 

 

C.2  Check valve/filters blocked by debris

 

C.3  Recirculation loop not piped properly 

 

 D. Discharge temperature too hot or cold
 

D.1  Valve not calibrated properly

 E. Hot water from cold water tap or cold from hot
 

E.1  Check valves fouled

 F. Valve is noisy
 

F.1  Water velocity is too high

 

F.2  Valve not sized properly

 G. No flow from valve
 

G.1  Hot or cold water supply failure or shutoffs closed 

 

G.2  Check valve/filters blocked by debris

 H. Flow from valve fluctuates 
 

H.1  Fluctuation in supply pressures

 

H.2  Check valve/filters blocked by debris

Answer

A.1  Check differential temperature between hot and cold supplies and 

outlet 10°F (5.6°C) minimum required

A.2 Reinstall valve with supplies connected to marked inlets
A.3 Clean filters

B.1  Measure supply pressures and check against flow chart. Look for 

restrictions in valve or piping

B.2 Clean check valves/filters 

 

C.1   Stabilize water pressures with pressure regulating or  

balancing valves

C.2  Clean check valves/filters
C.3   Pipe recirculated tempered water return so it connects 

to hot water source and cold side of Tempering valve  
(see Product Guide for piping details)

D.1  Readjust valve temperature per installation instructions

E.1  Clean check valves/filters

F.1  Reduce water velocity with pressure regulating valves
F.2  Check flow required versus rated flow capacity of valve 

G.1  Open shutoffs or restore hot and cold supply 
G.2  Clean check valves and filters

H.1   Stabilize water pressure with pressure regulating valves
H.2  Clean check valves and filters

Water  temperatures  in  excess  110ºF  (43ºC)  are  dangerous  and  may  cause 

scalding,  severe  injury  or  death!  This  valve  can  be  adjusted  to  deliver  water 

at  temperatures  exceeding  110ºF  (43ºC).  Consequently,  when  used  in  an 

ASSE  1016,  ASSE  1069  or  ASSE  1070  application,  the  installer  must  check 

the  mixed  water  outlet  temperature  at  the  point  of  use  and  adjust  the  Watts 

Thermostatic  Tempering  Valve  Series  MMV  or  LFMMV  to  ensure  delivery  of 

water at a safe temperature not exceeding 110ºF (43ºC). Mechanical valves are 

not fail-safe. Due to the effects of various water conditions, periodic verification 

of outlet water temperature is required.

When  used  in  an  ASSE  1017  application  at  the  hot  water  source,  the  Watts 

Thermostatic Tempering Valve Series MMV or LFMMV cannot be used by itself to 

control final temperature at fixtures where ASSE Standard 1016, ASSE 1069 or 

ASSE Standard 1070 listed devices are required. Such use may result in severe 

bodily  injury  (i.e.  scalding  or  chilling)  and/or  death.  Additional  ASSE  Standard 

1016, ASSE Standard 1069 or ASSE Standard 1070 listed devices, such as Watts 

Series L111, LFL111, USG, LFUSG, MMV or LFMMV should be used at fixtures 

to prevent possible injury.
Recirculation  systems  should  recirculate  water  at  temperatures  over  140ºF  to 

reduce the risk of bacterial growth in the piping. This valve should not be used 

to  achieve  these  elevated  temperatures.  This  valve  can  be  used  at  fixtures  in 

conjunction with recirculation systems to reduce the system’s hot water to a safe 

temperature at the point of use.

IMPORTANT

WARNING

!

Содержание MMV Series

Страница 1: ... remove unions and gaskets from valve body prior to soldering 7 After soldering flush piping and install valve using filter washer on hot and cold water inlet and fiber washer on the mixed water outlet 8 Start up Open cold water supply then hot water supply Inspect for leaks 9 Adjust temperature to desired setting see Temperature Adjustment Section Watts recommends a maximum temperature of 110 F 4...

Страница 2: ...ure Adjustment 1 Let the water flow for at least two minutes to allow supply temperature to stabilize 2 Calibrate the mixed water outlet temperature by placing a thermometer in the mixed water stream 3 To adjust the setting of the valve loosen locking cap screw with hex wrench see Figure 4 Cap must be lifted 1 4 to adjust temperature To increase the temperature turn coun terclockwise To decrease t...

Страница 3: ...and cold side of Tempering valve see Product Guide for piping details D 1 Readjust valve temperature per installation instructions E 1 Clean check valves filters F 1 Reduce water velocity with pressure regulating valves F 2 Check flow required versus rated flow capacity of valve G 1 Open shutoffs or restore hot and cold supply G 2 Clean check valves and filters H 1 Stabilize water pressure with pr...

Страница 4: ...ost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control This warranty shall be invalidated by any abuse misuse misapplic...

Отзывы: