SECTION 3: Operation
L- OMM-006_0A
•
1/26/2022
Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
11
of
38
•
A 1⁄4" FNPT port and pressure gauge has been installed in the filter's lid to indicate
working pressure . A second gauge is installed downstream of the filter in the pipe line to
indicate pressure differential and help determine when cartridge replacement may be
necessary.
3.6.
Lync UV Controller
The Lync UV controller features are:
•
Automatic lamp dimming for cooler operation
•
Flow switch
•
Lamp out audible alarm
•
Glow cap lamp indicator
•
Graphic touch screen display to show key operational data
•
Alarm output for solenoid valve
•
UV sensor input
•
4-20 milliamp output for UV Intensity (when UV Sensor is used).
3.6.1. UV Controller Wiring
Top Cat 5- Future Accessories
Bottom Cat 5- UV Sensor
Alarm Relay A (Left to Right)
Normally
Closed/Common/
Normally Open
Alarm Relay B (Left to Right)
Normally Closed/Common/
Normally Open
Power Input AC 100-240 VAC
50/60HZ
Right- Ground to Chassis
Center- Flow Switch
Left- Antenna Wire
4-20mA Transmitter (Left is
'Loop +', Right is 'Loop -')
Future Accessories