CALIBRATING CONTROL COMPONENTS
A T T E N T I O N
The control equipment should be serviced by qualified and authorized staff only. Incorrect
calibration settings can cause serious damage to the unit and injuries to people.
The control equipment is entirely calibrated and tested in the factory before the unit is shipped.
However, after the unit has been working for a reasonable period of time, the safety devices
should be checked. The calibration settings are shown in Table 2.
Control and safety components
Activation set point
Differential
Safety valve setting: high pressure side
1740 PSI [120 bar]
n/a
Safety valve setting: low pressure side
1160 PSI [80 bar]
n/a
High pressure switch setting
1566 PSI [108 bar]
1160 PSI [80 bar]
Low pressure switch setting
290 PSI [20 bar]
580 PSI [40 bar]
Anti-freeze alarm setting
39°F (4°C)
11°F (6°C)