Installation

 

  A.  Series 909/LF909 should be installed in a horizontal and upright 

position. This positions the relief valve below the first check 

valve, enabling the zone to drain through the relief valve outlet. 

The shutoff valve with the test cock is to be mounted on the inlet 

side of the backflow preventer. The test cock is on the inlet side 

of the shutoff valve.

  B.  The 909/LF909 should always be installed in an accessible loca-

tion to facilitate testing and servicing. Check the state and local 

codes to insure that the backflow preventer is installed in compli-

ance, such as the proper height above the ground.

  C.  Water discharge from the relief valve should be vented in accor-

dance with code requirements. The relief valve should never be 

solidly piped into a drainage ditch, sewer or sump. The dis-

charge should be funneled through a Watts air gap fitting piped 

to a floor drain.

  D.  Watts recommends a strainer be installed ahead of Watts 909 

Series assemblies to protect the discs from unnecessary fouling.

  E.  Backflow preventers should never be placed in pits unless abso-

lutely necessary and then only when and as approved by local 

codes. Consult your local or state plumbing or health inspector. 

Watts recommends installation indoors or above ground in an 

insulated enclosure.

Start Up

  F.  The downstream shutoff should be closed. Open upstream 

slowly, fill the valve and bleed the air through Test cock 2, 3 and 

4. When valve is filled, open the downstream shutoff slowly and 

fill the water supply system. This is necessary to avoid water 

hammer or shock damage.

  G.  The installation of a Watts air gap with the drain line terminating 

above a floor drain will handle any normal discharge or nuisance 

spitting through the relief valve. However, floor drain size may 

need to be designed to prevent water damage caused by a cat-

astrophic failure condition. Do not reduce the size of the drain 

line from the air gap fitting.

  H.  Two or more smaller size valves can be piped in parallel (when 

approved) to serve a larger supply pipe main. This type of instal-

lation is employed where increased capacity is needed beyond 

that provided by a single valve and permits testing or servicing of 

an individual valve without shutting down the complete line.

The number of assemblies used in parallel should be determined by 

the engineer’s judgement based on the operating conditions of a 

specific installation.

Indoors

Above Ground

Parallel

Now available, WattsBox Insulated Enclosures, for more information, send for ES-WB.

Min. 12” (300mm)

Watts 909/LF909
2

1

2

" – 10" (65 – 250mm)

Strainer

Air Gap

Watts 909S/LF909S FDA
2

1

2

” - 10” (65 - 250mm)

Meter

Strainer

Main

Air 

Gap

12” (300mm)

support

TaBlE OnE - capaciTy REQuiREd FOR sysTEM

50 GpM

100 GpM

150 GpM

200 GpM

250 GpM

350 GpM

Two 

3

4

"

Two 1"

Two 1

1

4

"

Two 1

1

2

"

Two 1

1

2

"

Two 2"

Devices

Devices

Devices

Devices

Devices

Devices

450 GpM

640 GpM

1000 GpM

2000 GpM

3000 GpM

5000 GpM

Two 2

1

2

"

Two 3"

Two 4"

Two 6"

Two 8"

Two 10"

Devices

Devices

Devices

Devices

Devices

Devices

Table shows total capacity provided with dual valve installations of various sizes.

Содержание LF909

Страница 1: ...this Manual for future reference Basic Installation Instructions NOTICE The flange gasket bolts for the gate valves should be re tight ened during in stal la tion as the bolts may have loos ened due to stor age and ship ping High Capacity Relief Series Location and Installation Considerations 1 Backflow preventers must be installed in high visibility locations in order to allow for immediate notic...

Страница 2: ...n its proper order The gate valve with the test cock is to be mounted on the inlet side of the backflow preventer The test cock must be on the inlet side of the wedge Please see above Failure to reassemble correctly will result in possible water damage due to excessive discharge from the relief port vent and possible malfunction of the backflow pre venter 8 Installation procedures must comply with...

Страница 3: ...e is filled open the downstream shutoff slowly and fill the water supply system This is necessary to avoid water hammer or shock damage G The installation of a Watts air gap with the drain line terminating above a floor drain will handle any normal discharge or nuisance spitting through the relief valve However floor drain size may need to be designed to prevent water damage caused by a cat astrop...

Страница 4: ...sh Print Head wait then Push Start Test 7 Open VA then slowly open VB no more than 1 4 turn When relief valve drips push the hold button for 2 seconds Record reading must be 2 psid or more Push Stop Test 8 Close VA and VB Test No 2 Test No 2 Check Valve 9 Install bypass hose between VA and TC 4 Open VA then bleed air by loosening hose connection at TC 4 Tighten hose connection Close VA Push Start ...

Страница 5: ...two spring retainers and the stem The spring re tainers are not to be removed for servicing If there is a need to re place the spring spring retainer or stem an assembled module must be obtained from the factory These modules are not interchangeable be sure to replace the first check with a first check mod ule and the second check with a second check module 6 To replace the disc on sizes 21 2 4 65...

Страница 6: ...embly 5 Removal of the bottom plug and spring assembly During nor mal field service there is no need to remove the bottom plug spring assembly other than inspection It can be removed by simply unscrewing with a large pipe wrench CAUTION The spring as retained on the bottom plug is highly loaded NO attempt should be made in the field to remove the spring For replacement a complete bottom plug assem...

Страница 7: ...place relief valve seat or inlet cover Electrically ground the piping system and or electri cally isolate the device with plastic pipe immediately upstream and down stream of the device B 6 Valve improperly reassembled B 6 If valve is dis as sem bled during installation caution must be exercised to install check springs in their proper location C Valve exhibits high pressure drop C 1 Fouled strain...

Страница 8: ...ost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control This warranty shall be invalidated by any abuse misuse misapplication improper insta...

Отзывы: