Series LF70A

Hot Water Extender Tempering Valves

IS-70A

*

A valve should be installed in cold water line to hot water extender tempering valve, as shown, to 

help compensate for pressure drop through heater.

 

NOTICE

†  

Valves listed to ASSE Standard 1016, 1069 or 1070 such as Watts Series LFMMV or LFUSG-B 

should be used at fixture to prevent possible injury.

Thermostat and Bonnet Assembly

(B)

(C)

(D)

Repair Kit 

Model 

Ordering Code

LF70ARK 

fits LF70A, LF70AT 

0125129

LFL70ARK 

LFL70A, LFL70AT 

0125130

Includes O-ring and (B), Spring (C) and Thermostat 

Assembly (D) 

(A)

Installation Instructions

Valve should be installed by a licensed contractor.

1.

 Close both the hot and cold water shutoff valves upstream of the valve.

2.

 Bleed pressure from the system.

3.

  Remove the thermostat and bonnet assembly (A), which is hand-tight, from body and 

install valve body as illustrated in diagram. Valve must be trapped 8" to 12" as shown.

4. 

 Reinsert Thermostat and Bonnet assembly in body and tighten knurled portion of bonnet 

securely with pliers or channel locks.

5.  START UP REQUIREMENTS: 

 Open cold water then hot water shutoff valves. The cold 

water supply line to Series LF70A valve should always be opened first to prevent possible 

thermostat damage.

Adjustment

The Series LF70A features a new adjustment means which permits you to “dial” a temperature 

quickly and conveniently. To increase or decrease the water temperature, simply turn the adjust-

ing cap as indicated by the arrow. The adjustment temperature range is 120°F to 160°F and will 

vary depending on system water pressure changes and water temperature fluctuations.

Model LFL70A:

  For lower tempered water or below 130°F, use low temperature Model LF-

L70A which provides a temperature range between 100°F-130°F.

NOTICE

  Model LFL70A (low temperature model) may be used in a radiant heat appli-

cation. Other models of this valve must not be used in radiant heat applications. When installing 

an LFL70A valve in a radiant heat application, the components of the radiant heat system must 

be of materials with a construction of withstanding the high limit output temperatures of the 

heating boiler. If you are uncertain as to the products adaptability for your application, please 

consult an authorized representative before installing or using the product.

NOTICE

BE SURE TO REMOVE THERMOSTATIC ASSEMBLY from valve before 

sweating connections, otherwise it will become damaged.

Minimum Flow Requirements to Maintain Set Temperature: 2 gpm for size 

1

2

" and 

3

4

"

Watts Vacuum  

Relief Valve

Cold

Watts  

T&P Relief Valve

Drain

Tempered

Hot to 

Appliances

Water Heater

Watts 

LF70A 

Watts 

Ball Valve

8" 

to 12"

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property  

damage, or damage to the equipment.
Keep this Manual for future reference.

 

CAUTION

!

Need for Periodic Inspection

Periodic inspection by a licensed contrac-

tor is recommended. Corrosive water condi-

tions, temperatures over 210°F, unauthor-

ized adjustments or repair could render the 

valve ineffective for service intended. Regu-

lar cleaning and checking of thermostat as-

sembly (A) helps to assure maximum life and 

proper product function. Frequency of clean-

ing depends upon local water conditions.

  

†See Warning.

Watts Hot Water Master Tempering Valves cannot be used for  

tempering water temperature at fixtures. Severe bodily injury (i.e., 

scalding or chilling) and/or death may result depending upon system 

water pressure changes and/or supply water temperature changes. 

ASSE standard 1016, 1069 or 1070 listed devices such as Watts 

Series LFL111, LFMMV and LFUSG and valves should be used at fix-

tures to prevent possible injury.

The Watts Hot Water Tempering Valves are designed to be installed at 

or near the boiler or water heater. They are not designed to compensate 

for system pressure fluctuations and should not be used where ASSE 

standard 1016, 1069 or 1070 devices are required. These Watts valves 

should never be used to provide “anti-scald” or “anti-chill” service.

WARNING

!

NOTICE

Inquire with governing authorities for local installation requirements