Installation, Maintenance, & Repair 
Series 007 and LF007

Double Check Valve Assemblies

Sizes: 

1

2

" – 3"

NOTICE

For Australia and New Zealand, line strainers should be installed 

between the upstream shutoff valve and the inlet of the backflow 

preventer.

3

4

" 007M3QT

RP/IS-007

Watts product specifications in U.S. customary units and metric 

are approximate and are provided for reference only. For precise 

measurements, please contact Watts Technical Service. Watts 

reserves the right to change or modify product design, construc-

tion, specifications, or materials without prior notice and without 

incurring any obligation to make such changes and modifications 

on Watts products previously or subsequently sold.

Testing

For field testing procedure, refer to Watts installation sheets  

IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on 

Watts.com.

For other repair kits and service parts, refer to our Backflow 

Prevention Products Repair Kits & Service Parts price list PL-RP-

BPD found on 

Watts.com.

For technical assistance, contact your local Watts representative.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property 

damage, or damage to the equipment.
Keep this Manual for future reference.

Installation Instructions

Series 007 and LF007

1

2

" - 2"

Indoors - 

Figure 1

Check local codes for installation requirements. Pipe lines should 

be thoroughly flushed to remove foreign material before installing 

the unit. A strainer should be installed as shown, ahead of backflow 

preventer to prevent disc from unnecessary fouling. Install valve 

inline with arrow on valve body pointing in the direction of flow.
For indoor installations, it is important that the valve be easily acces-

sible to facilitate testing and servicing. Do not install in a concealed 

location.
 

CAUTION

!

Do not install with strainer when backflow preventer is used on 

seldom-used water lines which are called upon during emergen-

cies, such as fire sprinkler lines, etc.
It is important that Series 007 and LF007 be tested periodically in 

compliance with local codes, but at least once a year or more often 

depending upon system conditions. Regular inspection, testing and 

cleaning assures maximum life and proper product function.

 

NOTICE

Fire Protection System Installations
The National Fire Protection Agency (NFPA) Guidelines require a 

confirming flow test to be conducted whenever a “main line” valve 

such as the shutoff valves or a backflow assembly have been oper-

ated. Certified testers of backflow assemblies must conduct this 

test. The trim valves of the detector meter bypass line, on assem-

blies so equipped, should be shutoff during the confirming flow test. 

When the test is completed, the trim valves must be returned to a 

fully open position.

Meter Box Installation

Local building or plumbing codes may require modifications 

to the information provided.  You are required to  

consult the local building and plumbing codes prior to 

installation.  If the information provided here is not consis-

tent with local building or plumbing codes, the local codes 

should be followed.  This product must be installed by a 

licensed contractor in accordance with local codes and 

ordinances.

WARNING

!

Need for Periodic Inspection/Maintenance:

  This product 

must be tested periodically in compliance with local codes, but 

at least once per year or more as service conditions warrant.  

All products must be retested once maintenance has been 

performed.  Corrosive water conditions and/or unauthorized 

adjustments or repair could render the product ineffective for the 

service intended.  Regular checking and cleaning of the product’s 

internal and external components helps assure maximum life and 

proper product function. 