Installation Instructions:

 

a.  Turn off all electrical power to the water heater.

 

b.  Turn off the water supply to the water heater.

 

c.   Drain water from the water heater so that the cold water supply piping is free of water.

 

d.  Close the drain valve after draining water.

1.   Install the Control Unit on the cold water supply piping with the arrow on the valve pointing in the direction of fl ow, towards the 

water heater. 

Figure 1

CAUTION: Do not apply heat directly to the valve body!
Pre-solder the adapter fi ttings that will be used to connect piping to the valve. Use caution when soldering to avoid damage 

to the valve cover and internal components.

2.   After soldering the piping to the fi ttings, apply thread sealant to the adapter fi ttings and thread the adapters with attached piping 

into the valve body.

 Figure 2

3.   Install and solder the piping to the supply and to the inlet of the water heater.
4.   Install the Water Detector Pad under the water heater with the green circuit board down. The Water Detector Pad must lie fl at on 

the fl oor or in a drain pan. Route the connecting cable to the Control Unit and insert the interlocking connector to the circuit board.

 

Figure 3

Note: 

It is not necessary to remove the cover of the Control Unit to install the interconnecting cables. To remove an interlocking cable, 

use the supplied Pocket Screwdriver to depress the tab on the cable while pulling cable from its socket. 

Figure 4

Important:

 Interconnecting wires must not touch or be in close proximity to any fl ame or hot surface.

 

a.   If no drain pan exists, install the Water Dam around the perimeter of the water heater. The Water Dam can be cut so that it fi ts 

approximately 1 to 2 inches outside the diameter of the water heater and includes the area where the Temperature and Pressure 

safety relief drain tube terminates.

 

b.   Install the plastic connector supplied with the Water Dam into both ends of the Water Dam so that no gap exists between the 

ends. 

Figure 5 and Figure 5a

5.   Install the Power Cutout Module, 

Figure 6,

 to the water heater as indicated below. 

Oil Fired Water Heater Installation (for Spark Ignition Water Heater Installation, see page 3)

NOTE:

  Be certain to disconnect the circuit breaker/fuse that supplies power to the oil burner. A warning label should be applied to the 

panel with a warning against restoring power while work is in process.

1. Mount the Power Cutout Module 

Figure 10,

 as close to the oil burner as possible.

2. Remove the jumper from the TT terminals of the oil burner relay shown in Figure 7.

Figure 1

Figure 2

Figure 3

Figure 4

Figure 5

Figure 5a

Figure 6

Содержание FloodSafe WDS-SI Series

Страница 1: ...er Detector Shutoff should be installed within 6 to 12 inches of the water heater on the cold water inlet supply pipe The Control Unit which houses the circuitry for the operation of the valve contains interlocking connectors for the Water Detector Pad the Power Supply and remote alarm and the Power Cutout Module The cables provided should not be cut or extended therefore remote installation is no...

Страница 2: ...sary to remove the cover of the Control Unit to install the interconnecting cables To remove an interlocking cable use the supplied Pocket Screwdriver to depress the tab on the cable while pulling cable from its socket Figure 4 Important Interconnecting wires must not touch or be in close proximity to any flame or hot surface a If no drain pan exists install the Water Dam around the perimeter of t...

Страница 3: ...f the cable Connect the cable from the Power Cutout Module Figure 14 Terminal C common to the SPARK terminal of the Electronic Control and NO normally open to the Pilot Electrode Assembly as indicated in Diagram 2 Figures 12 and 13 Note We have made every effort to provide all of the hardware required for a complete installation However the terminal connections used to connect the Pilot Electrode ...

Страница 4: ... to the Control Unit can occur Exceeding the current rating will void the warranty Figure 18 IMPORTANT Do not insert the Power Supply into the 120 VAC outlet until the installation is complete 7 Insert the green circuit board connector into the Control Unit Figure 19 8 Check the position of the valve reset located on the front of the Control Unit The slots should indicate the valve is in the open ...

Страница 5: ...3 If all of the above functions take place the unit can be reset To Reset the Control Unit 1 Remove the Water Detector Pad from the drain pan or Water Dam and wipe the moisture from the green circuit board 2 Wipe any water from the drain pan or Water Dam 3 Reposition the Water Detector Pad on the floor or in the drain pan 4 Turn the valve position indicator on the Control Unit to the open position...

Отзывы: