Troubleshooting

Check Procedure with Differential Pressure Gauge

CHECKLIST

READING

PROBLEM

Check differential across check valve No. 1

2 to 3 psid

Leak in check valve No. 1 or No. 2

6 to 8 psid and steady

Malfunctioning pressure relief valve

2 to 7 psid and steady

Inlet pressure fluctuating

Check differential across check valve No. 1 

2 to 3 psid 

Check valve No. 1 held open

6 to 8 psid and steady 

Malfunctioning pressure relief valve

Check Procedure Without Differential Pressure Gauge

CHECKLIST

READING

PROBLEM

Close gate valve No. 2 

If discharge stops 

Leak in check valve No. 2

If discharge does not stop 

Try the next remedy

Open test cock No. 4 to produce a flow greater than the  
differential relief valve discharge

If discharge stops

Leak in check valve No. 1

If discharge does not stop

Malfunctioning pressure relief valve

PROBLEM

CAUSE

SOLUTION

Continuous discharge from relief valve during NO FLOW 
conditions (Discharge stops with water flow) With this 
symptom, the pressure drop across check valve No. 1 
would be 2 to 3 psid. If a flow of water (more than dis-
charge) is created through the valve, the pressure drop 
should increase to approximately 7 psi

Debris fouling check valve No. 1

Inspect and clean

Outlet pressure highter than inlet pressure and deris  
fouling check valve No. 2
Spring stem not moving freely

Inspect for dirt or other foreign material

Damaged seat or seat disc

Inspect and replace (If necessary, the seat disc can be 
reversed in sizes ½" to 2".)

Leakage at check module O-ring

nspect and replace seal or O-ring

Intermittent discharge from relief valve during NO FLOW 
conditions. With the symptom, the pressure drop across 
the check valve No. 1 would vary from about 2 to 7 psid 

Inlet line pressure variations causing relief valve to  
discharge

Eliminate or reduce pressure variations by installing a soft-
seated, spring-loaded check on upstream side of device

Pressure surges (water hammer) causing relief valve to 
discharge as pressure wave passes through the zone

Eliminate or reduce pressure surges

Continuous discharge from relief valve during FLOW and 
NO FLOW conditions With this symptom, the pressure drop 
across the check valve No. 1 would be 7 psid or more at 
all time

Seat disc dislodged from cavity in  the main stem  
(This can be caused  by pressure surges during initial  
filling of  system lines.) 

Reposition disc in main stem cavity
Repressurize system slowly

Debris fouling the relief valve seat

Inspect and clean

Debris blocking the relief valve sensing passage
Dirt or scale jamming main stem

Inspect and clean, or replace

Leakage at main stem

Relief valve does not open above  
2.0 psid during field testing

Outlet gate valve not closed completely

Inspect and clean

Plugged low pressure hydraulic passage (from “ZONE” to 
inner diaphragm)
Improper alignment of internal parts during reassembly 
(causing high resistance to movement)

Reassemble

Jammed main stem due to debris blocking gate valve

Clean

Check No. 1 pressure drop is low (less than 5 psid) during 
field testing

Debris fouling first check seat

Inspect and clean

Debris fouling second seat with backpressure
Inlet pressure variations causing inaccurate gauge reading

Eliminate pressure variations by installing a soft-seated, 
spring-loaded check on upstream side of device

Damaged seat or seat disc

Inspect and clean as required

Worn guide, bushing, or stem

Inspect and replace as required

Check No. 2 fails to hold back pressure during field testing

Outlet gate valve not closed completely

Inspect and clean

Debris fouling second check seat
Damaged seat or seat disc

Inspect and replace if required

Worn guide, bushing, or stem

Содержание FEBCO 860 Series

Страница 1: ...s to discourage tampering or install a protective enclosure to discourage vandals When opting for an enclosure install the protective cover so that adequate clearance is available for maintenance and...

Страница 2: ...ng assemblies of both check valves and open the inlet shutoff valve to allow sufficient flow of water through the assembly Clear all sand debris and other particles from the line If debris in the wate...

Страница 3: ...semblies are disassembled and reassembled in the same manner To service the checks replace the check modules with new ones by using check module assembly kits available from FEBCO Or replace the rubbe...

Страница 4: ...e from the relief valve assembly may not indicate a relief valve failure Water is discharged from the relief valve when the mainline check valves become fouled with foreign debris For more information...

Страница 5: ...may become folded or creased if the internal assembly is restricted while tightening the cylinder 7 Replace the O ring Item 20 in the relief valve cover Properly seat the round bead on the large diaph...

Страница 6: ...certain conditions relief valves can discharge water at rates greater than the air gap drain capacity 2 For an indoor installation locate the assembly near a floor drain sized to adequately handle dis...

Страница 7: ...Seat Ring RV 1 12 1 Gasket Ring RV 1 13 Spring RV 1 14 Seat Disc RV 1 15 Diaphragm RV 1 16 Outer Diaphragm RV 1 17 Small Piston RV 1 17 1 Round HD Screw RV 1 17 2 Washer RV 1 17 3 Hex Nut RV 1 18 Cyl...

Страница 8: ...1 1 4 2 32 50 Both checks Kit includes Items 2 2 3 1 qty 2 and 5 qty 2 Relief Valve Rubber Kit 905345 ALL 1 2 3 4 15 20 905345 ALL 1 25 905346 ALL 1 1 4 2 32 50 Kit includes Items 12 12 1 14 15 16 18...

Страница 9: ...se the outlet ball valve After clearing the system with air partially open the outlet ball valve 7 Leave all drain valves test cocks and ball valves in the half open half closed position for the winte...

Страница 10: ...line pressure variations causing relief valve to discharge Eliminate or reduce pressure variations by installing a soft seated spring loaded check on upstream side of device Pressure surges water hamm...

Страница 11: ...capabilities to the relief valve of an existing installation in a BMS configuration For Cellular Communication ORDERING CODE ADD ON RETROFIT KIT DESCRIPTION 88009432 FP FBF CFS Cellular Flood Sensor C...

Страница 12: ...damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or...

Отзывы: