Setting of FLU is by means of relative screw; fully tighten the screw to obtain
minimum flow rate setting, fully loosen the screw to have maximum flow rate
setting. The following table gives the values for limiting flow rate settings in m

3

/h

in relation to the pipe diameter. The FLU flow switch is supplied with the setting
screw fully tightened (minimum setting).

For applications in heating systems subject to I.S.P.E.S.L. approval in accordance
with the requirements of Body R, where a safety action is requested (switching off
of the motor-driven pump  under an abnormal condition), it is advisable to leave
the setting at minimum, bearing in mind that the device acts on the burner when
the flow rate drops below the value given in the bold-face column.

FLU

Flow switch for liquids, for
piping from 1" to 8".

0401125     1”

IP64

0401126     1”

IP67

Part No.     Size     Protection

FLU is a flow switch which interrupts the electric control
circuit of the burner when  there is insufficient water
circulation in the boiler circuit owing to some abnormal
condition (e.g. stopping of the motor -driven pump). 
The  FLU flow switch is operated thanks to an electrical
blade-type tripping device (stainless steel blade) and can
be installed on pipework from 1" to 8" in size.

APPLICATION AND OPERATION

Mount so that the direction indicated by the arrow
coincides with the flow.
For correct operation it is advisable:

- to mount on the return pipe

- to mount on horizontal pipe (mounting on vertical piping
is possible after appropriate setting)

- to keep a certain distance from sources of turbulence
(elbows, valves, etc.); recommended min. distance is
equal to 5 times the pipe diameter

- to keep a minimum distance of 55 mm between the
pipework and the lower base of the appliance.

INSTALLATION

The 1-2 contact is normally open (closes when the flow
rate setting is reached); contact 1-3 is normally closed
(opens when the flow rate setting is reached). Earth con-
nection is through relative screw located at the bottom on
the microswitch support.

ELECTRICAL CONNECTIONS

Conformity with Body R of I.S.P.E.S.L. regulations
CE mark in  conformity with European Directives EEC
89/336, EEC 73/23.

APPROVALS

ADJUSTMENT OF FLOW RATE SETTING

1”

34

0,9

0,4

2,0

1,5

1” 

1/4

34

1,2

0,6

2,6

1,9

1” 

1/2

57

1,6

0,9

3,3

2,6

2”

57

3,2

2,3

7,1

5,1

2” 

1/2

88

4,2

3,5

8,0

7,0

3”

88

6,3

5,7

12,0

10,5

4”

88

13,5

12,0

28,0

26,0

4”

167

8,0

7,1

20,0

18,0

5”

88

27,0

23,0

60,0

58,0

5”

167

12,1

9,0

30,0,

28,0

6”

88

43,0

36,0

91,0

37,0

6”

167

17,2

12,0

35,0

32,0

8”

88

85,0

73,0

176,0

170,0

8”

167

42,0

36,0

90,0

85,0

Overall dimensions (mm)

DESIGN FEATURES

Casing and cover

Die-cast aluminium

Bellows

Phosphor bronze

Blade

Stainless steel (*)

Fitting

Brass, 1" M

(*) Blade length varies according to the pipe diameter (see table)

TECHNICAL CHARACTERISTICS

Contact load rating

6 (2) A at 250 V ~ at 50 Hz

Max. fluid pressure

10 bar

Max. fluid temperature

110°C

Max. room temperature

60°C

Degree of protection

IP 64 for Art. 0401125

IP67 for Art. 0401126

(*) also available in the version with microswitch   20 (8) A at 250 V ~.

NORMALLY 
OPEN

NORMALLY
CLOSED

Pipe

Blade 

Flow rate with                   Flow rate with

diameter

length 

minimum setting              maximum setting

(screw fully tightened)       (screw fully loosened) 

inches

mm

m

3

/h

m

3

/h

close           open            close           open         

Содержание DOLOMIT IGD Series

Страница 1: ...LIQUIDS Flow switches interrupt an electrical control circuit when the water circulation fails in the circuit for some abnormal condition e g stop ping of motor driven pumps They are operated thanks t...

Страница 2: ...e cable cable colour Blue Brown Black allows float switch Series IGD to be used for emptying or filling depending on the electrical connections as described below Emptying Black Brown connection conta...

Страница 3: ...act size although still retaining electrical and float characteristics such as to ensure perfect operation Product reliability is ensured thanks to the sound expe rience of WATTS Cazzaniga in the sect...

Страница 4: ...keep a certain distance from sources of turbulence elbows valves etc recommended min distance is equal to 5 times the pipe diameter to keep a minimum distance of 55 mm between the pipework and the lo...

Страница 5: ...istance is equal to 5 times the pipe diameter to keep a minimum distance of 55 mm between the pipework and the lower base of the appliance INSTALLATION The 1 2 contact is normally open closes when the...

Страница 6: ...switch ADJUSTMENT OF SET PRESSURE Contact b c is normally closed it opens when the set pressure is reached Connection to earth is via terminal a View of the terminal board from above after removing t...

Страница 7: ...SET PRESSURE Contact b c is normally closed it opens when the set pressure is reached Connection to earth is via terminal a View of the terminal board from above after removing the cover ELECTRICAL CO...

Страница 8: ...es com e mail info wattscazzaniga it The descriptions and photographs contained in this product specification sheet are supplied by way of information only and are not binding WATTS CAZZANIGA reserves...

Отзывы: