Centurion Pre-Installation Electrical Power Guide
TAG-0104_A
• 4/18/2023
• (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 4 of 6
3.
PROVISIONS FOR SERVICE
Designers must provide emergency shutoffs and other devices to satisfy electrical codes. It is
also recommended to provide an electrical shutoff disconnect switch of suitable load carrying
characteristics on or near each Centurion water heater.
•
No electrical boxes or field components should be mounted to the surface of the unit or
where they might interfere with the removal of the side or top panels for maintenance.
•
The service disconnect switch should be mounted near the unit (Figure 2-1).
•
Wiring conduit, EMT, or other wiring paths should be supported externally, not secured
to the unit.
•
Electricians should be instructed as to where the wiring conduit should be located, such
as away from the relief valve discharge, drains, etc.
•
All electrical conduit and hardware should be installed so that it does not interfere with
the removal of any covers, inhibit service or maintenance, or prevent access between
the unit and walls or another unit.
4.
WATER HEATER WIRING
A dedicated protected circuit should be provided from the power source to the water heater. No
other electrical devices should be permanently wired on the same circuit.
The protected circuit
and circuit breaker switch must be sized for the amperage values below.
An emergency switch (electrical shutoff) must be wired in series with power to the unit.
Connecting an emergency shutoff switch (E-stop) to the main power terminals of the water
heater is the recommended and safest way to totally disable and un-power the unit. Use of the
remote interlock, located on the I/O board, is not recommended since it does
not
cutoff power
within the unit, it only disables it. Under no circumstance should the remote interlock of the
WHM Manager unit be used as an emergency switch for the plant.
Figure 4-1
– Water Heater Wiring Diagram
The following table lists the input power requirements for all Centurion water heaters, including
the diagram number of each model’s corresponding schematic diagram:
Diag. Voltage/Phase/Frequency MOCP Wires
1
208V / 3
/ 60 Hz
20 A
5
2
460V / 3
/ 60 Hz
15 A
4