manualshive.com logo in svg
background image

Setting the Sustaining Control

STEP 7

Slowly open downstream isolation valve to establish flow through 

the system.

STEP 8

Setting the Sustaining Control requires lowering the upstream 

pressure to the desired minimum sustained pressure.

STEP 9

Leave the downstream isolation valve full open and close the up-

stream isolation valve until the inlet pressure drops to the desired 

setting.

Fine-tune the Reducing Control adjustment to the pressure reduc-

ing setpoint, as detailed in Step 7.

STEP 10

Adjust the Sustaining Control screw IN, clockwise, until the inlet 

pressure begins to increase, or OUT, counterclockwise, to de-

crease, stopping at the desired pressure (See Figure 2).

4          IOM-A-ACV-920-15_620-15   2115 

EDP# 1917048 

© 2021 Watts

IOM-A-ACV-920-15_620-15   2115 

EDP# 1917048 

© 2021 Watts         5

Figure 2 

PV20C — Pressure Sustaining Control

Clockwise to increase inlet 

pressure

Counterclockwise to decrease 

inlet pressure

Содержание Ames 920GD-15

Страница 1: ...Setting the Pressure Controls 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the inf...

Страница 2: ...the upstream zone The valve will close if necessary until upstream pressure is above the pilot setting The valve should be specified to include the optional opening speed control and position indicato...

Страница 3: ...ed air by loosening a fitting on the valve or a plug at the highest point of the valve as sembly STEP 5 Pressure the line by opening the upstream isolation valve slowly Air is vented through the air b...

Страница 4: ...valve until the inlet pressure drops to the desired setting Fine tune the Reducing Control adjustment to the pressure reduc ing setpoint as detailed in Step 7 STEP 10 Adjust the Sustaining Control sc...

Страница 5: ...counterclockwise increasing the rate of closing IF INSTALLED Opening Speed Flow Control Adjustment The Opening speed flow control allows free flow into the cover and re stricted flow out of the cover...

Страница 6: ...specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm...

Страница 7: ...djust opening speed control to verify functionality adjust as required Standard setting for open ing speed control is 1 1 2 2 1 2 turns open from full closed position Can be adjusted in field Main Val...

Страница 8: ...move cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require...

Страница 9: ...rush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thread...

Страница 10: ...ts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrit...

Страница 11: ...el 9 Stem Washer ASTM A276 304 Stainless Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iro...

Страница 12: ...resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no cont...

Отзывы: