Modulex EXT Commercial Series Boilers User Manual
CHAPTER 6: Operation of the E8 Controller
Page
108
of
144
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0095_0H
09/15/2017
Phone: 800-526-0288
GF-139
TABLE 6-7: 0-10V Signal with Slope and Temperature
Curve
U1
U2
T1
T2
UA
0
2.0 V
10.0 V
32° F
194° F
2.0 V
1
2.5 V
0.3 V
100° F
176° F
5.0 V
2
2.5 V
0.3 V
100° F
167° F
5.0 V
3
2.5 V
0.3 V
100° F
113° F
5.0 V
4
4.0 V
0.1 V
68° F
185° F
5.0 V
5
4.0 V
0.1 V
68° F
167° F
5.0 V
6
4.0 V
0.1 V
68° F
131° F
5.0 V
7
4.0 V
0.1 V
68° F
189° F
5.0 V
8
4.0 V
0.1 V
68° F
189° F
5.0 V
9
4.0 V
0.1 V
68° F
163° F
5.0 V
10
4.0 V
0.1 V
68° F
127° F
5.0 V
11
4.0 V
0.1 V
68° F
194° F
5.0 V
6.10.2 Setting of DHW Circuit
Operation of Pumps In Parallel
6.10.2.1
Heating pump operation during DHW production.
EXPERT menu
⇒
Hot Water
⇒
F-PUMP PARAL “00,01,02,03”
Use of a DHW Storage Tank Thermostat (On/Off)
6.10.2.2
To use an ON - OFF thermostat instead of DHW sensor.
EXPERT menu
⇒
Hot Water
⇒
THER IMPUT “01”
Antilegion
6.10.2.3
Activation of an antilegion program.
EXPERT menu
⇒
Hot Water
⇒
ANTILEGION “01”
Setting for Solar Panel Use
6.10.2.4
Use a PT 1000 sensor as a solar panel sensor.
EXPERT menu
⇒
Solar/ MF
⇒
FUNC RELAY 4 “23”
6.11 ACCESS CODE SETTING
To set the access code, press the Programming button to enter the first parameter, use the data
knob to select a number, and then press the Programming button to accept the value. Repeat
this procedure for each code number position.
Figure 6-11: Setting the Access Code