Modulex Light Commercial Series
CHAPTER 4: Installation Instructions
OMM-0158_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
39
of
120
W A R N I N G !
•
Before commissioning the boiler, fill the condensate drain pipe with water, at the dedicated
filling-up plug. See Figure 4-18.
•
Do not install the condensate drain where freezing may occur.
•
Use materials approved by the authority having jurisdiction in your area. In the absence of
such authority, PVC and CPVC pipe must comply with ASTM D1785, F441 or D2665. Cement
and primer must comply with ASTM D2564 or F493.
•
For Canada, use ULC certified PVC or CPVC pipe, fittings and cement.
•
Periodic cleaning of the condensate disposal system must be carried out.
4.17 Water Treatment
The chemical/physical composition
of the heating system’s water is fundamental for the boiler’s
correct operation and safety.
Among the problems caused by poor quality of feed water, the most frequent and the most serious
is the buildup of deposits on boiler thermal exchange surfaces.
Less frequent but also serious are deposits on the water circulating piping surfaces. Because of
the low thermal conductivity of mineralization desposits from improperly treated water, the thermal
exchange efficiency may be seriously reduced and result in dangerous localized overheating.
AERCO suggests treating and conditioning feed water for the heating circuit in the following:
•
When the hardness of the water is higher than 9 grains per gallon (gpg).
•
For cold/hot water installations with large water content.
•
Renewal of the water system due to uncontrolled leakages.
•
Subsequent refilling of the system due to maintenance work on the installation.
•
Presence of different metals in the water circuit.
Properly treated system and feed water will substantially reduce the following problems:
•
lime scale deposit
•
corrosion sludge
•
deposits
•
microbiological growths (molds, bacteria etc.)
An appropriate treatment of the supply water will prevent the above stated problems and will
maintain the correct operation and efficiency of the boiler over time.
In order to properly treat water for use in a hydronic boiler heating system, the following
physical/chemical characteristics must be addressed.
Sediment:
If sediment is present in the system, a sediment filter or other appropriate device, must
be used.
Water pH:
If water has a pH above 8, or below 6.5, then the water must be treated to provide a
medium pH of between 6.5 and 8.
The system water to be judged for water characteristics should be taken from the return pipe of
the primary circuit downstream of the circulating pump.