Benchmark 5000-6000 Operation & Maintenance Manual
SECTION 2: OPERATION
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 20 of 148
2.5 SETUP Menu
The
Setup
menu (Table 2-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-out
after 1 hour. Therefore, the correct password must be reentered when required. In addition to
permitting password entries, the
Setup
menu is also used to enter date and time, and units of
temperature measurements. A view-only software version display is also provided to indicate
the current C-More Controller software version.
TABLE 2-3: SETUP Menu
MENU ITEM DISPLAY
AVAILABLE CHOICES OR LIMITS
DEFAULT
Minimum
Maximum
1
Password
0
9999
0
2
Language
English
English
3
Time
12:00 am
11:59 pm
4
Date
01/01/00
12/31/99
5
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
6
Comm Address
0
127
0
7
Baud Rate
2400, 4800, 9600, 19.2K
9600
8
onAER Mode
Ethernet or SD Card
Ethernet
9
Min Upload Timer
0
9,999 Sec
0
10
Unit Alpha
E, G, H, R, N or A
A
11
Unit Year
0
99
0
12
Unit Serial #
0
9999
0
13
Software
Ver 0.00
Ver 9.99
Current software
version