CHAPTER 6: SAFETY DEVICE TESTING
PR2: 04/22/13 Page
69
of
158
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
Operation and Maintenance Manual
OMM-0052_0E
GF-127
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
Figure 6-3: Manual Gas Shut-Off Valve Location (Partial Left-Side View)
6.10 AIR FLOW FAULT TESTS
These tests check the operation of the Blower Proof Switch and Blocked Inlet Switch shown in
Figure 6-3.
1. Disable the blower output drive voltage as follows:
(a) Press the MENU key until
CONFIGUR-ATION MENU
is displayed.
(b)
Press the ▲ arrow key until the
ANA-LOG OUTPUT
function is displayed, then
press the
CHANGE
key.
(c)
Press the ▼ arrow key until
OFF
is displayed, then press the
ENTER
key.
2. Start the unit in the Manual Mode at a valve position of 34%.
3. The unit should shut down and execute an
IGNITION RETRY
cycle by performing the
following steps:
(a) The unit will execute a 30 second re-ignition delay and display
WAIT RETRY
PAUSE.
PROPANE
SSOV
MANUAL
GAS
SHUTOFF
VALVE
BLOWER
PROOF
SWITCH
AIR/FUEL
VALVE
BLOCKED
INLET
SWITCH
NATURAL
GAS
SSOV