Quick Installation Guide

 

AM Series

 

QIG-0001_0A

   

      11/1/2019          

Technical Support

  

  (800) 526-0288  

  Mon-Fri, 8 am - 5 pm EST          Page 3  of 7 

 

 

 

 

  

POTABLE APPLICATIONS 

MINIMUM FLOW 

 

10 grains/gal max

 

200ppm TDS max

 

POTABLE APPLICATIONS 

MINIMUM FLOW

 

18 grains/gal max

 

200ppm TDS max

 

AM 199

 

11 gpm

 

18 gpm

 

AM 250

 

12 gpm

 

18 gpm

 

AM 399

 

22 gpm

 

37 gpm

 

AM 500

 

24 gpm

 

37 gpm

 

AM 750

 

36 gpm

 

60 gpm

 

AM 1000

 

48 gpm

 

75 gpm

 

WATER PIPING: 

 

Boiler applications:  

 

Use primary/secondary piping configuration.  

 

Common pipe diameter must be sized for less than 4.0 ft/sec; common pipe length must 

be 3 to 5 times its diameter. 

 

Single unit application - relocate supply temperature sensor from boiler header to system 

piping. 

 

Multiple unit application - install Cascade header temperature sensor in the system piping 

(see AERCO Cascade Sequencer user manual (GF-146-CS) for installation details). 

Water heating applications: 

 

A storage tank must be used. See below for basic 

piping configurations. 

 

An anti-scald valve must be used and installed in 

accordance with local codes. 

Ensure that the minimum system flow is met 
per chart and table below, otherwise the flow 
sensors will automatically stop the burner.  

AM SERIES PRESSURE DROP 

A: AM 199/250; Min flow (high fire) =11 gpm/ 12 gpm 
B: AM 399; Min flow (high fire) =22 gpm 
C: AM 500; Min flow (high fire) =24 gpm 
D: AM 750; Min flow (high fire) =36 gpm 
E: AM 1000; Min flow (high fire) =48 gpm

 

Содержание AERCO AM Series

Страница 1: ... 1 Neutralizer media 4 Adjustable foot 1 Outdoor sensor boiler models only 1 Piping kit for circulation pump AMRI models only shipped loose ALCOVE CLOSET INSTALLATIONS Follow rules on clearances venting ventilation openings as per the O M and the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or CAN CSA B149 1 Natural Gas and Propane Installation Code and local codes DO NOT use non metallic exhaus...

Страница 2: ...ess Steel Polypropylene CPVC PVC For Alcove Closet Installation use Al29 4C only Do not use PVC exhaust for applications where return water temperature 145F See O M for additional information Polypropylene and Al29 4C exhaust requires additional adapters contact the vent manufacturer for suitable adapter Vent material must be sealed to specification of its manufacturer Do not use EPDM seals VENT A...

Страница 3: ...ingle unit application relocate supply temperature sensor from boiler header to system piping Multiple unit application install Cascade header temperature sensor in the system piping see AERCO Cascade Sequencer user manual GF 146 CS for installation details Water heating applications A storage tank must be used See below for basic piping configurations An anti scald valve must be used and installe...

Страница 4: ... Fri 8 am 5 pm EST Page 4 of 7 BOILER APPLICATIONS WATER HEATING APPLICATIONS with Integrated Tank The condensate drain must slope down and away from the boiler into a drain it must be installed accordingly in order to avoid the freezing of the liquid WATER HEATING APPLICATIONS Separate Tank ...

Страница 5: ...ly Terminals 101 102 PE Low Water Cut Off Terminals 103 104 Primary Pump boiler loop Terminals 113 114 Constant Setpoint Enable Disable if employed otherwise jumped Terminals 10 11 Set Para 2003 0 Outdoor Sensor if employed Terminals 14 15 Set Para 2003 1 Outdoor Reset See O M for additional settings for Outdoor Reset 0 10VDC if employed Terminals 22 23 Set Para 2003 4 0 10V Notes on 0 10VDC analo...

Страница 6: ...tion Module on each unit AM399 1000 factory installed AM199 250 optional Refer to the AM Series MODBUS User Manual GF 146 MB for wiring and setup details Controls Panel Button Functions To access Installer Menu Para 2000 s Hold B and S 5 seconds until G appears Scroll through parameters R S Select parameter B value blinks Change parameter value R S Confirm new value B Exit Installer Menu Hold B 5 ...

Страница 7: ... install combustion analyzer probe 8 after the flue gas exhaust connection 2 Start unit per procedure on this page 3 Set unit to standby Press A boiler or S water heater until OFF is displayed 4 Set Para 2201 AM 399 1000 or 2010 AM 199 250 to HIGH 5 Generate demand Press C boiler or R water heater until setpoint is above OFF e g 90F 6 Wait 2 3 min for CO2 to stabilize 7 Compare CO2 reading with hi...

Отзывы: