background image

Troubleshooting Guide - Backflow Preventers

Problem

Cause

Solution

A.

Valve spits periodically from the vent

A.1

Fluctuating supply pressure.

A.1

Install a soft seated check valve immediately
upstream of the device. 

A.2

Fluctuating downstream pressure

A.2

Install a soft seated check valve downstream of 
the device close as possible to the shutoff valve. 

B.

Valve drips continually from the vent

B.1

Fouled first check

B.1

Flush valve. If flushing does not resolve problem, 
disassemble valve and clean or replace the first 
check.

B.2

Damage or fouled relief valve seat.

B.2 

Clean or replace the relief valve seat.

B.3

Relief valve piston O-ring not free to

B.3 

Clean, grease or replace the piston O-ring.

move due to pipe scale, dirt or build
up of mineral deposits.

B.4

Excessive back pressure, freezing, or

B.4

Eliminate source of excessive backpressure or

water hammer has distorted the

water hammer in the system downstream of the 

second check.

device. Use Watts No. 15 to eliminate water ham-
mer. Replace defective second check assembly.
In case of freezing; thaw, disassemble and inspect 
internal components.
Replace as necessary.

B.5

Electrolysis or relief valve seat or first

B.5

Replace relief valve seat or inlet cover. 

check seats.

Electrically ground the piping system and/
or electrically isolate the device with plastic pipe 
immediately upstream and downstream of 
the device.

B.6

Valve improperly reassembled.

B.6

If valve is disassembled during installation, 
caution must be exercised to install check springs 
in their proper location.

C.

Valve exhibits high pressure drop.

C.1

Fouled strainer.

C.1

Clean strainer element or replace.

C.2

Valve too small for flows encountered.

C.2

Install proper size device based upon
flow requirements.

D.

No water flows downstream of valve.

D.

Valve installed backwards.

D.

Install valve in accordance with flow
direction arrow.

E.

Valve does not test properly

E.1

Follow manufacturer's test procedure

E.1, E.2 

Clean or replace gate valve with full port ball 
valves or resilient wedge shutoff valves.

E.2

Leaky downstream gate valve.

F.

Valve quickly and repeatedly fouls following servicing.

F.

Install finer mesh strainer element in the strainer.

F.

Debris in pipe line is too fine to be
trapped by strainer.

G.

Winterization of backflow preventers.

G.

Electric heat-tape wrap closely together around 
valve body. Build a small shelter around the valve 
with a large light bulb installed and left on at all times.
If supply line is not used during the winter, removal 
of the complete body is the best. This would create
an air gap to eliminate any possible backflow.

7

Содержание 909RPDA

Страница 1: ...TO THE PRODUCT THE COMPANY MAKES NO OTHER WARRANTIES EXPRESS OR IMPLIED THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRA...

Страница 2: ...t the safe drinking water as per applicable standard Figure 1 Series 909 RELIEF VALVE DISCHARGE RATES ZONE PRESSURE PSIG FLOW RATE GPM Installation Note The flange gasket bolts for the gate valves sho...

Страница 3: ...Test cock 2 3 and 4 When valve is filled open the downstream shutoff slowly and fill the water supply system This is necessary to avoid water hammer or shock damage G The installation of a Watts air...

Страница 4: ...drips push the hold button for 2 seconds Record reading must be 2 psid or more Push Stop Test 8 Close VA and VB Test No 2 Test No 2 Check Valve 9 Install bypass hose between VA and TC 4 Open VA then...

Страница 5: ...3 RK 909 S 8 200 0887734 RK 909 S 10 250 Kits include Seat Seat O ring Cover O ring Retainer wire and lubricant Total Rubber Parts Kits 0887750 RK 909 RT 21 2 3 65 80 0887751 RK 909 RT 4 100 0887752 R...

Страница 6: ...Bottom plug o ring and lubricant Relief Valve Total 0887235 RK 909 VT 21 2 3 65 80 0887236 RK 909 VT 4 6 100 150 0887237 RK 909 VT 8 10 200 250 0887238 RK 909M1 VT 4 10 100 250 Kits include Adapter o...

Страница 7: ...lve seat or inlet cover check seats Electrically ground the piping system and or electrically isolate the device with plastic pipe immediately upstream and downstream of the device B 6 Valve improperl...

Страница 8: ...web site at www watts com RP IS 909 909RPDA 0829 EDP 1915172 2009 Watts USA 815 Chestnut St No Andover MA 01845 6098 www watts com Canada 5435 North Service Rd Burlington ONT L7L 5H7 www wattscanada c...

Отзывы: