background image

1.

   Backflow preventers must be installed in high-visibility 

locations in order to allow for immediate notice of telltale  

discharge or other malfunction. This location should 

also facilitate testing and servicing, and protect against  

freezing and vandalism.

2.

   Installing a backflow preventer in a pit or vault is not 

recommended as flooding of the pit will cause a cross- 

connection. Ensure that 

all local codes and required 

safety provisions are met

. An air gap below the relief port  

must be maintained so as to avoid, flooding and sub-

mersion of the assembly, which may lead to a cross-

connection.

3.

   A strainer should be installed ahead of the backflow 

preventer to protect all internal components from un- 

necessary fouling.

  

CAUTION -

 Do not install a strainer ahead of the backflow 

preventer on seldom-used, emergency water lines (i.e.  

fire sprinkler lines). The strainer mesh could potentially be-

come clogged with debris present in the water and cause  

water blockage during an emergency.

4.  

Normal discharge and nuisance spitting are accommo-

dated by the use of a Watts air gap fitting and a fabricated  

indirect waste line. Floor drains of the same size 

MUST

 

be provided in case of excessive discharge.

5.  

When a 909 Series backflow preventer is installed 

for dead-end service applications (i.e. boiler feed 

lines, cooling tower makeup or other equipment 

with periodic flow requirements), discharge from 

the relief vent may occur due to water supply 

pressure fluctuation during static no-flow condi-

tions. A check valve may be required ahead of the  

backflow preventer. *Please see “Troubleshooting”, 

page 7, 

prior to installation

.

6.  

The 909 Series backflow preventer is designed so that 

the critical level of the relief valve is positioned below the  

first check. This unique feature allows the valve to be 

installed either vertically or horizontally

.

7.

  

Installation procedures must comply with all state 

and local codes.

 *Please see page 3 for specific in- 

stallation procedures.

8.

   Prior to installation, thoroughly flush all pipe lines to 

remove any foreign matter.

9.

  

Start up

 at Initial Installations and After Servicing: The 

downstream shutoff should be closed. Slowly open 

upstream shutoff and allow the backflow preventer to 

fill slowly. Bleed air at each test cock. When backflow 

preventer is filled, slowly open the downstream shutoff 

and fill the water supply system. This is necessary to 

avoid dislodging O-rings or causing damage to internal 

components.

10.   Test:

 The 909 Series backflow preventer must be tested 

by a certified tester at the time of installation in order 

to ascertain that the assembly is in full working order 

and may be relied upon to protect the safe drinking 

water as per applicable standards.

 How It Operates

The unique relief valve construction 

incorporates two channels: one for air, 

one for water. When the relief valve 

opens, as in the accompanying air-

in/water-out diagram, the right hand 

channel admits air to the top of the 

reduced pressure zone, relieving the 

zone vacuum. The channel on the left 

then drains the zone to atmosphere. 

Therefore, if both check valves foul, 

and simultaneous negative supply and 

positive backpressure develops, the 

relief valve uses the air-in/water-out 

principle to stop potential backflow.

Repair Parts:

 Use only original equipment, manufactured parts  

to protect the validated warranty.

First 

Check

Relief 

Valve

Second 

Check

909QT

Reduced 

Pressure 

Zone

Water Out

Air In 

2

Basic Installation Instructions

Watts 

3

4

" – 2" (20-50mm) 909QT High Capacity Relief Series: 

Location and Installation Considerations

Содержание 909 Series

Страница 1: ...E COMPANY MAKES NO OTHER WARRANTIES EXPRESS OR IMPLIED THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANT...

Страница 2: ...ofthereliefvalveispositionedbelowthe first check This unique feature allows the valve to be installed either vertically or horizontally 7 Installation procedures must comply with all state and local c...

Страница 3: ...d in an accessible location to facilitate testing and servicing A discharge line should be piped from the air gap at the relief valve connection making sure there is adequate drainage Never pipe the d...

Страница 4: ...No 2 Step 2 Close test cock No 4 Disconnect bypass hose yellow at test cock No 4 Step 3 Open needle valve B low blue and C bypass yellow bleeding to atmosphere then closing needle valve B blue restor...

Страница 5: ...el Seat Second Check Kits 0887121 RK 909 CK2 3 4 1 20 25 0887134 RK 909 CK2 11 4 2 32 50 0887123 RK 909 CK2SS 3 4 1 20 25 0887136 RK 909 CK2SS 11 4 2 32 50 Kit includes Disc assembly Spring Seat Seat...

Страница 6: ...4 1 20 25 0887371 RK 909 SV 11 4 2 32 50 Kit includes Seat Seat o ring Piston o ring and lubricant Note 11 4 2 32 50mm 909 909M1 share a common kit To Prevent Shaft Damage Assemble As Shown Caution If...

Страница 7: ...s not resolve problem disassemble valve and clean or replace the first check B 2 Clean or replace the relief valve seat B 3 Clean grease or replace the piston O ring B 4 Eliminate source of excessive...

Страница 8: ...eb site at www watts com RP IS 909S 1111 EDP 0834246 2011 Watts USA No Andover MA Tel 978 688 1811 Fax 978 794 1848 www watts com Canada Burlington ON Tel 905 332 4090 Fax 905 332 7068 www wattscanada...

Отзывы: