Auto-Zone CV & CV-EX
Section 4
Start-Up and Troubleshooting
4-17
Troubleshooting
The following is a guide to assist in troubleshooting the CV and CV-EX systems. It is
provided as a systematic approach to determining and resolving common system
problems.
General Communications
No CV Units are communicating
♦
Is the CommLink connected and plugged in?
♦
For CV is the CommLink jumper set for single loop operation? See Figure 4-3
♦
For CV-EX systems is the CommLink jumper set for multiple loop operation? See
Figure 4-3
♦
Are Comm Loop voltages correct? See the Comm Loop troubleshooting section.
♦
Is the Comm Loop open or shorted?
♦
Are the CV Controller address switches set correctly? See
Figure 4-7
.
♦
Are the CV Controllers powered? Check 24 VAC to the controllers.
♦
Is the Communications Loop shorted? Check Comm Loop voltages.
♦
Is the System Manager connected to the Communications loop?
Some CV Units are communicating but others are not:
♦
Are the CV Controller address switches set correctly? See the addressing chart.
♦
Are the CV Controllers powered? Check 24 VAC to the controllers.
♦
Is the REC LED on the missing CV Controller “flickering”? See
Figure 4-
6 for
location of the REC LED.
♦
Is the COMM LED on the CV Controller blinking an error code? See the Blink Code
chart.
♦
Are Comm Loop voltages correct at the missing unit? See the Comm Loop trouble-
shooting section.
firealarmresources.com
Содержание Auto-Zone CV
Страница 1: ...Design Installation And Operations Manual CV CV EX System Revision 01B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 12: ...firealarmresources com...
Страница 38: ...firealarmresources com...
Страница 102: ...Section 4 Auto Zone CV CV EX 4 36 Start Up and Troubleshooting Notes firealarmresources com...
Страница 103: ...firealarmresources com...