The Dimming Curve LED will blink according to load type below.

CURVE/LOAD TYPES

Dimming Curve

Load Type

Curve 1 - 1 blink 

followed by a pause, 

then repeats.

Incand/MLV/ELV/LED/

Neon/cold cathode

Curve 2 - 2 blinks 

followed by a pause, 

then repeats.

2 wire fluor (Advance 

Mark X or equal)

Curve 3 - 3 blinks 

followed by a pause, 

then repeats.

3 wire Lutron (Hi-Lume 

or Eco-10)

Step 3: Repeat steps 1 and 2 for the second load. 
Step 4: Exit Dimming Curve Selection
To exit Dimming Curve Selection simply release the Load 
Override Button.  

IMPORTANT NOTE: THE DIMMING CURVE MUST 

BE SET FOR PROPER OPERATION.

Load On/Off/Dimming

Override Buttons

Load Status: Blue LEDs

Dimming Curve: Yellow LED

Red
LED

Config
Button

Dimming Curve Button

Button Selection Location and LEDs

DIMMING CURVE SELECTION

Dimming Curve Selection Procedure

The Dimming Curve button allows selection of the appropriate 

curve for the connected load type.
By default the curve is factory set to curve 1 which is for 
incandescent, MLV, ELV, LED, and neon/cc loads. 
Step 1: Load Selection

 

Press and hold the Load button for the load that you wish to 

configure. 

 

The lights will dim down/up in a continuous cycle.

Step 2: Curve Selection 

 

While continuing to press and  hold the Load ButtonTap 

and release the Dimming Curve Button to select the correct 
curve

 

for the connected load type (see Curve/load types). 

Each subsequent tap of the dimming curve button will cycle to the 

next curve. This will be indicated by the frequency at which the 

yellow Dim Curve LED is blinking (see Curve/load types).

0341373638

Serial 

Number

Room

Controller

Load

Control

LMRC-222

3

4

0575852231

Master

0341373638

LMRC-222

1

2

A

B

A

B

0574762112

In a DLM local network 

with only LMRC-222 

room controllers, the 

LMRC-222 with the 

highest serial number 

is the Master, carrying 

Load 1 and 2. The next 

highest serial number 

would have Load 3 and 

Load 4,  and so forth.

Load A ON/OFF/Dim button

Blue LED  

ON when 

load is ON.

Load button: 

Press & 

release for 

ON/OFF.

Press & hold 

to Dim.

Load B ON/OFF/Dim button

PLUG n

’ GO OPERATION (P

nG)

Plug n’ Go supports the most energy efficient control 

strategy.  For example, if at least two loads, one switch 

and one occupancy sensor are connected to the DLM local 

network, the system operates load A as Automatic ON, 

Automatic OFF and load B as Manual-On, Automatic-Off. 
See DLM device Quick Start Guides to determine how each 

device affects the PNG operation of the LMRC-222.

Load Control Arbitration

To take full advantage of automatic PnG configuration, 

review these simple rules about load control arbitration. 
After the room controllers are connected to the DLM Local 

Network and powered up they automatically negotiate 

to determine which controller becomes the Master and 

assigns the load numbers for each load output on the DLM 

Local Network.

The Master is the controller with the highest serial 

number. The LMRC-222 has two load outputs. 