LMRC-222
Digital Lighting Management (DLM)
2 Load Universal Dimming Room Controller
Ins
tatllation Ins
tructions
Corner Mount
Occupancy
Sensor
Switch/
Dimmer
Ceiling Mount
Occupancy
Sensor
J Box
To
Load
LMRC-222
Room
Controller
Daylighting
Sensor
DLM Local Network
(low voltage, Class 2)
LMRJ cables
PLACEMENT EXAMPLE
Specifications
Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . 120/277VAC, 50/60Hz
Minimum Load Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 watt
Maximum Load Ratings
Incandescent, Quartz Halogen, LED Drivers* . . . . . . . . . . . . . 20A
Magnetic Low Voltage* Transformer (MLV) . . . . . . . . . . . . . . 20A
Electronic Low Voltage* Transformer (ELV) . . . . . . . . . . . . . . 20A
Electronic Fluorescent Dimming Ballasts . . . . . 1920 W @ 120 V
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4432 W @ 277 V
- 2 Wire Advance® Mark X or equal
- 3 Wire Lutron® Hi-Lume or Eco-10
- Neon/Cold Cathode (cc)
* Forward Phase compatible, dimming rated only
Output to DLM Local Network . . . . . . . . . . . . . up to 250mA @ 24VDC
DLM Local Network Characteristics when using LMRC-222:
Provides low voltage power over Cat 5e cable (LMRJ); max current
800mA. Free topology up to 1,000’ max.
Environment:
Operating Temperature. . . . . . . . . . . . . .32° to 131°F (0° to 55°C)
Storage Temperature . . . . . . . . . . . . . .23° to 176°F (-5° to 80°C)
Relative Humidity. . . . . . . . . . . . . . . . . 5 to 95% (non condensing)
Max Branch Circuit Overcurrent Protection . . . . . . . . . . . . . . . . . 25A
For full operational details
see the DLM Dimming
System Installation Guide
and Dimming System
Addendum provided with
the room controller and
also available at
www.wattstopper.com
I
NSTALLATION SHALL BE
IN ACCORDANCE WITH ALL
APPLICABLE REGULATIONS,
LOCAL AND NEC CODES.
Wire connections shall be rated
suitable for the wire size (lead
and building wiring) employed.
WARNING:
TO CONNECT A COMPUTER
TO THE DLM LOCAL NETWORK USE
THE LMCI-100.
NEVER CONNECT
THE DLM LOCAL NETWORK TO AN
ETHERNET PORT
– IT MAY DAMAGE COMPUTERS
AND OTHER CONNECTED EQUIPMENT.
CAUTION:
TURN THE
POWER OFF AT THE CIRCUIT
BREAKER BEFORE WIRING.
120/277VAC, 50/60Hz
Class 2 output: 250mA
Compatible loads:
• 20A @ 120/277V: Incandescent, MLV, ELV and LED
(forward phase compatible)
• 1920 W @ 120V, 4432 W @ 277V: neon/cc, 2 wire
and 3 wire electronic fluorescent dimming ballasts
- 2 wire (Advance® Mark X or =)
- 3 wire (Lutron® Hi-Lume or =)
UL 2043 Plenum Rated
2 load Universal Dimming Room Controller
LMRC-222
75 C Copper Wire Only
120/277VAC, 50/60Hz
Class 2 output: 250mA
Compatible loads:
• 20A @ 120/277V: Incandescent, MLV, ELV and LED
(forward phase compatible)
• 1920 W @ 120V, 4432 W @ 277V: neon/cc, 2 wire
and 3 wire electronic fluorescent dimming ballasts
- 2 wire (Advance® Mark X or =)
- 3 wire (Lutron® Hi-Lume or =)
UL 2043 Plenum Rated
2 load Universal Dimming Room Controller
LMRC-222
75 C Copper Wire Only
Santa Clara, CA • 800.879.8585
Industrial Control
Equipment
46A9
Indoor Use Only
MOUNTING THE CONTROLLER
The room controller mounts to a four square deep junction
box using the included mounting plate with the hinge pins
extending away from the box as shown.
Terminate wiring according to wiring diagram.
Slide the rubber
hinge stopper into the
hinge slot as shown
to secure the unit.
Line Voltage Wiring
Mounting plate
Tighten mounting
screw using
screwdriver.
WARNING:
TO REDUCE RISK OF
ELECTRIC SHOCK. UNIT SHALL
BE PROPERLY GROUNDED IN
ACCORDANCE WITH NEC AND LOCAL CODES.