background image

SENSOR 
PLACEMENT

Sensor

Ceiling

COVERAGE PATTERN

Coverages shown are maximum and represent 
half-step walking motion. 

10ft

0

8ft

8ft

16ft

16ft

0

10 15ft

55ft

85 90ft

Top View

Side View

Quick Start Guide

LMPX-100-1

Digital Lighting Management

PIR Corner Mount 

Occupancy Sensor

Long Range Lens

Line

Voltage

Room

Controller

J-Boxes

Daylight Sensor

Switch

Switch

Corner Mount

Sensor

Ceiling Mount

Sensor

DLM Local Network

Low Voltage

LMRJ Cables

Loads

2

1

Line/Hot

Black wire

Neutral

White wire

Red wire

to Load A (1)

Yellow wire

to Load B (2)

LMRC

102

Room
Controller

J Box

Occupancy
Sensor

Switch

To

Load/Line

(Class 1 wiring)

DLM Local Network 

(low voltage, Class 2)

LMRJ Cables

CONNECTIVITY

The illustrations below show examples of free-topology wiring. The LMPX-100-1 communicates to all other Digital Lighting 
Management devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network. 

Voltage  ................................................................................ 24VDC

Current Consumption ............................................................ 7mA

Power Supply .............. Watt Stopper/Legrand Room Controllers

Connection to the DLM Local Network ....................... RJ-45 plug

DLM Local Network Characteristics:
 

Provides low voltage power over Cat 5e cable (LMRJ).

 

Supports up to 24 communicating devices, including 4 

 

LMRC-10x or LMPL-101 max per each DLM Local Network.

 

Free topology up to 1,000ft of low voltage cable.

Environment ................................................. For Indoor Use Only

 

Operating Temperature ....................32° to 131°F (0° to 55°C)

 

Storage Temperature ...................... 23° to 176°F (-5° to 80°C)

 

Relative Humidity ...........................5 to 95% (non condensing)

Patent Pending

THIS UNIT IS PRE-SET FOR PLUG n’ GO™ 

OPERATION, ADJUSTMENT IS OPTIONAL.

For full operational details, adjustment and more 

features of the product, see the DLM System 

Installation Guide provided with the LMRC-102 and 

also available at

 

www.wattstopper.com

INSTALLATION SHALL BE 
IN ACCORDANCE WITH ALL 
APPLICABLE REGULATIONS, 
LOCAL AND NEC CODES.

Intended for Listed Class 
2 DLM Devices.

For Class 2 DLM devices - 
To be connected to a Class 
2 power source only.

For Class 2 Device Wiring Only – 
Do Not Reclassify and Install as 
Class 1, or Power and Lighting 
Wiring.

Wire connections shall be rated 
suitable for the wire size (lead 
and building wiring) employed.

10 ft.

Отзывы: