Watt Stopper DT-300 Скачать руководство пользователя страница 13

MANUAL ON FUNCTION

The Manual 

ON

 function is facilitated by installing a momentary switch such as 

Watt Stopper LVS-1 Momentary Toggle Switch, or RS2-3 Low Voltage Momentary 

Switch. The switch connects to the sensor’s Manual (Man.) Switch and +24V 

terminals as shown in the wiring diagram. Each time the switch is pressed, the load 
changes state. The sensor’s operation as related to the manually operated switch is 
determined by DIP switch settings for Occupancy Logic.

Manual Mode

 (Trigger Option 6 or 7): In this mode, the switch 

is required

 to turn on 

the load. The sensor keeps the load on, based on occupant activity. After the time 
delay ends, if there is no movement detected within the 30 second re-trigger period, 
the load turns 

OFF

 and the manual switch must be used to turn 

ON 

the load.

Automatic Mode

 (any Trigger Option except 6 or 7): These options use occupancy 

triggers as well as switch activation to turn the load 

ON

. A manual switch provides 

the following additional functionality:
a.  The load can be turned 

ON

 using the manual switch and it stays on according to 

the occupancy logic setting. The time delay operates as programmed. When the 
load turns 

OFF

 due to lack of occupancy detection, it can be turned 

ON

 again by 

occupancy detection or the switch.

b.  Activating the manual switch while the load is 

ON

 turns the load 

OFF

•  When the load is turned 

OFF

 manually, as long as the sensor continues to 

detect occupancy the load stays 

OFF

. The length of the time delay after the 

last occupancy detection, the lights stay off and the sensor reverts to the 
automatic-on mode. 

•  When the load is turned 

OFF

 manually, pressing the switch again turns the 

load 

ON

 and the sensor reverts to the automatic-on mode.

•  Once returning to automatic-on mode, either the switch or occupancy 

detection can turn the load 

ON

OVERLOAD PROTECTION

The occupancy sensor has a built in overload protection function that will 

automatically turn off the control output when the load current exceeds 

200mA.  The sensor LEDs will then blink rapidly (~ 10Hz) to provide 

a visual indication of an overload condition.  When the load current is 

corrected or returns to normal, the control output will turn back on. 

Visit our website for FAQs: www.wattstopper.com

Содержание DT-300

Страница 1: ...acks Isolated Relay Rating 1A 30VDC VAC Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minute...

Страница 2: ...to 30 minutes the lights are switched off A walk through mode can turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The DT 300 operates on 24V...

Страница 3: ...r a ceiling heights of about 8 12 feet Mounting above or below this range will significantly affect the coverage patterns As a general rule each occupant should be able to clearly view the sensor Mask...

Страница 4: ...verage 36 ft 10 97m PIR Coverage 36 ft 10 97m Sensor 20 Ultrasonic Overlap Call 800 879 8585 for Technical Support If the space is larger than 30 x 30 it will be necessary to use more than one sensor...

Страница 5: ...ge Momentary Switch to the above applications see wiring diagram Manual On wiring with low voltage momentary switch connect Wire from one side of switch to 24V terminal on sensor Wire from other side...

Страница 6: ...tage Class 2 Load 1 Load 2 Optional DT 300 Standard wiring with local off switch Rear Housing Depluggable Terminal Front Cover Ceiling Spring Clips 2 Blue Control Out 24V Common Low Voltage Class 2 Li...

Страница 7: ...s 2 Blue Control Out Black 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red DT 300 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch u...

Страница 8: ...voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low voltage wires to the appropriate terminals on the sensor 3 Loosen the appliance mounting screws attache...

Страница 9: ...e flashing to stop 3 Ensure that the Ultrasonic Sensitivity trimpot is set to about 70 clockwise 4 Remain still The red and green LEDs should not flash The lights should turn off after 5 seconds If no...

Страница 10: ...ngs If Test Mode is enabled after Light Level has been set Light Level functionality will cease to function throughout the duration of Test Mode When Test Mode period expires the Light Level functiona...

Страница 11: ...he pushbutton for 5 seconds or more resets the light to default maxi mum Press and hold the Light Level button for 5 seconds or until the detection LED s turn ON and then OFF the LEDs flash rapidly fo...

Страница 12: ...nge from Standby area unoccupied and loads are OFF to Occupied area occupied and loads are ON Both requires detection by PIR and Ultrasonic Either requires detection by only one technology PIR require...

Страница 13: ...ed ON using the manual switch and it stays on according to the occupancy logic setting The time delay operates as programmed When the load turns OFF due to lack of occupancy detection it can be turned...

Страница 14: ...high voltage is present replace the power pack Red LED does not flash 1 When power is initially applied to the sensor there is a warm up period of 30 to 60 seconds before the LED becomes active 2 Make...

Страница 15: ...z an overload condition exists When this is corrected the sensor will return to normal operation Check the blue wire connection If necessary replace the power pack Lights do not turn off automatically...

Страница 16: ...e manually controlled with a light switch if one is installed 3 Reconnect the blue wire Turn sensitivity and time delay to minimum and allow the sensor to time out If lights turn off the sensor is wor...

Страница 17: ...277VAC 50 60Hz 225mA 20A ballast or incandescent 1HP 120 250VAC BZ 150 Power Pack 120 277VAC 50 60Hz 225mA 20A ballast or incandescent 1HP 120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 6...

Страница 18: ...liabilities on the part of WattStopper for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property...

Отзывы: