6

2. Using the Watson-Marlow  external potentiometer (when fitted):

(1)

Apply mains power.

(2)

Start the motor using the I/0 switch and adjust the potentiometer to obtain the desired speed.

(3)

Reverse the direction of rotation using the  

 switch.

3. Using the OPm2 hand held controller to select a set running speed

(a)

Plug the OPm2 hand held controller  into the Trio (see Fig. 1)

(b)

Select the required language using the up key 

I

 and down key 

J

 and then press P (this screen only appears the first time

the OPm2 is plugged in).

(c)

To select the required running frequency: Press P and then s to parameter P005, Press P, then 

I

 or 

J

 to alter the default

setpoint (default value = 50Hz), Press P to store.

(d)

Press 

I

 to parameter P006. Change to 0 to specify digital input.

(e)

Press 

I

 to parameter P007. Change to 1 to enable the OPm2.

(f)

Press the Menu button and then select OPERATE using the P button.

(g)

Press the ON (I) button on the OPm2. The inverter will now run at the frequency set by P005. Adjust the frequency using the

I

 and 

J

 keys.

(h)

Adjust other parameters as required to suit operating conditions (see parameter summary list at rear of manual).

1 Motor current

2 Parameter number

3 Current status

4 Motor direction

5 F=current, S=setpoint frequency

6 Motor rpm

7 Motor voltage

8 Motor torque (% max)

Other OPm2 functions

The parameter settings required can be entered using the three buttons (P 

I

 and 

J

) on the front panel.

The parameter numbers and values are indicated on the LED display.

Pressing the Jog button while the inverter is stopped causes it to start and run at the preset jog frequency factory preset 5Hz. The
inverter stops as soon as the button is released. Pressing this button while the inverter is running has no effect. Disabled if P123
= 0.

Press I to start the inverter. Disabled if P121 = 0

Press 0 to stop the inverter.

Press 

 to change the direction of rotation of the motor. REVERSE is indicated by a minus sign (values <100) or a

flashing decimal point (values > 100). Disabled if P122 = 0.

Press 

I

 to INCREASE frequency. Used to change parameter numbers or values to higher settings during the

parameterisation procedure. Disabled if P124 = 0.

Press 

J

 to DECREASE frequency. Used to change parameter numbers or values to lower settings during the

parameterisation procedure. Disabled if P124 = 0.

P Press the access parameters. Disabled if P051 - P053 = 14 when using digital inputs.

Note:

If the motor does not run after parameters have been changed accidentally, reset the inverter to the factory default
parameter values by setting parameter P944 to 001 and then pressing  P.

 

5

 2

 

1

 

8

 

4

 

6

 

7

 3

Содержание 501 Trio

Страница 1: ...501 Trio 501tr gb 01 pdf ...

Страница 2: ...cted to malicious or accidental damage or electrical surge are excluded Warranties purporting to be on behalf of Watson Marlow Limited made by any person including representatives of Watson Marlow Limited its subsidiaries or its distributors which do not accord with the terms of this warranty shall not be binding upon Watson Marlow Limited unless expressly approved in writing by a Director or Mana...

Страница 3: ... power off and wait one minute so that the dc link capacitors can discharge Some parameter settings can start the motor automatically after a mains failure The Trio inverter is not to be used as an emergency stop mechanism a circuit breaker must be used Wiring connection details Remove the four M4 cross head screws on the Trio s cover to access the electrical terminals see Fig 2 Note A drip loop i...

Страница 4: ...ghtening torques are used Access cover retaining screws 2 5Nm Gland hole covers 1 0Nm Mains connector screws 1 0Nm Control connector PL700 0 4Nm Check the supply voltage is correct for the inverter used by referring to the rating label Control cable connections The control and power supply cables max 1mm diameter must be laid separately They must not be fed through the same cable conduit trunking ...

Страница 5: ...e link from DIN1 pin 5 and P10 pin 1 to DIN2 pin 6 and P10 pin 1 on the control cable connector see Figs 2 and 3 b Apply mains power The green and yellow LEDs will illuminate to show that power is applied Turn potentiometer R314 accessed by removing the right hand gland hole cover see Fig 2 fully counter clockwise otherwise the Trio cannot be started c Turn the potentiometer clockwise until the ye...

Страница 6: ...or direction 5 F current S setpoint frequency 6 Motor rpm 7 Motor voltage 8 Motor torque max Other OPm2 functions The parameter settings required can be entered using the three buttons P I and J on the front panel The parameter numbers and values are indicated on the LED display Pressing the Jog button while the inverter is stopped causes it to start and run at the preset jog frequency factory pre...

Страница 7: ...le on off switch This sets up the inverter for clockwise rotation default If counter clockwise operation is required connect a switch between control terminals 6 and 1 d Connect the OPm2 and set parameter P005 to the desired frequency setpoint e Set parameter P006 to 000 to specify digital setpoint f Set the external on off switch to on The inverter will now run at the frequency set by P005 6 Remo...

Страница 8: ...fault Switch off power and switch on again F012 External trip PTC Check if motor is overloaded F013 Programme fault Switch off power and switch on again F018 Auto restart after fault Automatic re start after fault P018 is pending WARNING The inverter may start at any time F030 PROFIBUS link failure Check the integrity of the link F031 Option module to link failure Check the integrity of the link F...

Страница 9: ... resistor hot System Parameters Note In the following parameter table l Indicates parameters that can be changed during operation Indicates that the value of this factory setting depends on the rating of the inverter If parameters are changed accidentally all parameters can be reset to their default values by setting parameter P944 to 1 and then pressing P Parameter Function Default Your setting P...

Страница 10: ... power for motor kW hp P086 l Motor current limit 150 P087 Motor PTC enable 0 P088 Automatic calibration 0 1 P089 l Stator resistance W P091 l Serial link slave address 0 P092 l Serial link baud rate 6 P093 l Serial link timeout seconds 0 P094 l Serial link nominal system setpoint Hz 50 00 P095 l USS compatibility 0 P140 Most recent fault code P141 Most recent fault code 1 P142 Most recent fault c...

Страница 11: ...cate for each pump returned RGA No 1 Company Address Postcode Telephone Fax Number 3 4 Cleaning fluid to be used if residue of chemical is found during 2 Product servicing 2 1 Serial Number a 2 2 Has the Product been used b YES NO c d If yes please complete all the following Sections If no please complete Section 5 only 3 Details of substances pumped 4 I hereby confirm that the only substances s t...

Отзывы: