bus is currently 0 for all records, so they are ignored by the parser. Also, Zone is a 1-based number.
Zone 0 is a special case that
denotes “self” or the
RMA PLUS in this case. Using Zone 0 is agnostic of
changes to the Watbus logical address. If you wish to use the system configuration file to set your
Ethernet parameters, change the bus to 1 for each record and verify the elements in the value column.
Add records to the file as necessary keeping the following in mind:
•
Unless otherwise specified, all numeric fields are base 10 (decimal).
•
The file may contain a maximum of 2000 valid records.
•
There is currently a maximum of 500 unique data points per Watbus bus and zone.
•
Writing to the parameters in this example will require two resets. The first reset writes the new
value to the Ethernet object, the second reset uses the new value to initialize communications.
NOTE: There are other parameters that will behave this way.
Bus
Segment
Zone
Class
Instance
Member
Representation
Value
0
0
0
70
2
16
15
1284
ETH 2 IP Address Mode (DHCP=1281 Fixed=1284)
0
0
0
70
2
55
9
192.168.0.100
ETH 2 Static IP Address
0
0
0
70
2
56
9
255.255.255.0
ETH 2 Static IP Subnet Mask
0
0
0
70
2
57
9
192.168.0.1
ETH 2 Static IP Default Gateway
Figure 50 - SysCfg.csv default configuration
Non-Volatile Memory
Software objects that contain non-volatile elements are stored in files in a protected partition of
memory on the NOR FLASH drive that cannot be accessed directly by users. Software tools such as
Dashboard may be used to modify these files indirectly.
Objects that have been changed are only saved to non-volatile memory after three seconds of inactivity.
This feature prevents pre-maturely wearing out NV memory due to constant writes. However, this also
implies that the user must wait at least three seconds before resetting the RMA PLUS to prevent losing
recent changes.
It is also important to note that since the protected volume (described above) and customer volume
exist on the same device, changes cannot be saved to non-volatile memory if the user has the NOR
FLASH drive mounted (locked).
Standard Objects
The RMA PLUS implements the following software objects. Conditional objects and / or instances are
highlighted in yellow.
Class ID
Qty
Comment
1
0x01
Device
2
If RMAP-(5,8)AXX-XXXX
2
0x02
Variable
20
3
0x03
Display
1
4
0x04
Analog Input
4
If RMAP-8AXX-XXXX
12
0x0C
Limit
4
If RMAP-8AXX-XXXX
14
0x0E
Custom Setup
2
16
0x10
Test
1
19
0x13
Assembly Setup
2
20
0x14
Assembly
2
25
0x19
Math
20
26
0x1A
Process Value
4
If RMAP-8AXX-XXXX
Содержание RMA PLUS RMAP-2A Series
Страница 1: ...Version 1 0 PN 2042 8198 Page 1 of 75 DN 10 32813 RMA PLUS User Manual...
Страница 8: ...Version 1 0 PN 2042 8198 Page 8 of 75 DN 10 32813...
Страница 11: ...Version 1 0 PN 2042 8198 Page 11 of 75 DN 10 32813 Figure 3 Ground Wire Location...
Страница 24: ...Version 1 0 PN 2042 8198 Page 24 of 75 DN 10 32813 Figure 20 RMA PLUS via USBD Eject start selected drive...
Страница 26: ...Version 1 0 PN 2042 8198 Page 26 of 75 DN 10 32813 Figure 22 RMA PLUS via USBD MICRO SD root...
Страница 27: ...Version 1 0 PN 2042 8198 Page 27 of 75 DN 10 32813 Figure 23 RMA PLUS via USBD NOR FLASH root...
Страница 29: ...Version 1 0 PN 2042 8198 Page 29 of 75 DN 10 32813 Figure 25 RMA PLUS via USBD Eject stop selected drive...
Страница 42: ...Version 1 0 PN 2042 8198 Page 42 of 75 DN 10 32813 Figure 37 Default web page Index html...
Страница 75: ...Version 1 0 PN 2042 8198 Page 75 of 75 DN 10 32813...