Watlow Power Series Скачать руководство пользователя страница 4

N20

100A

N20

80A

N20

65A

N25

140A

N25

105A

N25

85A

N30

165A

N30

120A

N30

105A

Ordering Information

POWER SERIES

P C _ _  -  _ _ _ _  - _ _ _ _

Microprocessor-based,
solid state power controller

Package Style
C = 65 to 250 amps

Phase
1 = 1 phase
2 = 3-phase/2-leg control, (4 SCRs)
3 = 3-phase/3-leg control, (6 SCRs)
4 = 3-phase/4-wire, wye

connected load

8 = 2 single-phase zones
9 = 3 single-phase zones

Heater Diagnostics
0 = None
1 = Heater diagnostics (required for any

heater current monitoring or current
limiting).

Output Amperage Rating 
(See amperage chart to the right)

Output Voltage Rating
A = 24 to 120V
B = 200 to 480V
C = 200 to 600V

Communications
0 = None
1 = EIA/TIA-232/485 communications,

opto-isolated (field selectable)

Feedback/Retransmit

0 = None
1 = Load current feedback (0-10V or 0-20mA scalable 

retransmit output) (Must have heater 
diagnostics selected)

Custom
00 = None
AA = No Watlow logo with agency approval marks
XX = Custom, consult factory for options

Your Authorized Watlow Distributor Is:

2 Zone and

3 Zone and

Single Phase

3 Phase, 2 Leg

3 Phase, 3 Leg

Code  Amperage    Code   Amperage    Code   Amperage

Amperage Chart—

50˚C (122˚F)

Non-Fan Cooled 

Fan Cooled 

F20

125A

F20

120A

F20

90A

F25

200A

F25

160A

F25

140A

F30

250A

F30

185A

F30

155A

Single Phase

3 Phase, 2 Leg

3 Phase, 3 Leg

Code  Amperage    Code   Amperage    Code   Amperage

Single Phase Configuration
This configuration can be purchased with any or all the 
features available on the POWER SERIES, based on 
customer preference. It is intended for resistive heaters,
but can also be used on transformer connected loads in 
the phase angle firing mode.
Three-Phase, Two Leg Configuration
This configuration is intended for zero cross firing only into 
a stable resistive heater. Typically, a three-phase delta or
ungrounded wye connected heater is used and only two of
the three V~ line phases are switched.The third phase 
is a direct connection through a bussbar on board the 
POWER SERIES. Heater current monitoring and kVA options 
are available via the heater diagnostics option.
Three-Phase, Three Leg Configuration
All POWER SERIES options are ava i l a ble with this 
c o n fig u ra t i o n . It wo rks well with phase angle firing into a 
t h r e e - p h a s e, three-wire wye or delta connected heater. In this
c o n fig u ration, the more common applications are tra n s fo rm e r
connected loads with heaters requiring a soft start and/or 
current limiting.
The three-phase, four-wire configuration is intended for zero
cross firing into a three-phase grounded wye/star heater (This
is a  separate hardware option, model number dependent.)  
Single-Phase, Multizone Configuration
This configuration is available in two and three single-phase
zones and all the features of a single-phase unit are 
available. (Note that there is only one alarm relay and all
zones in the controller must use the same control method.)
Heater Diagnostics
Heater diagnostics may include some or all of the 
features that require heater current monitoring, depending 
on the model selected. Heater current monitoring is only 
available with heater diagnostics installed on the controller.
The features dependent on heater current monitoring are
heater bakeout, current limiting, heater kVA monitoring,
retransmit and heater monitoring alarms such as open heater,
heater out of tolerance, load balance and shorted SCR 
detection/error. Heater diagnostics must also be installed 
if you need phase angle control with current limit.

North American Sales Offices:

Atlanta, (770)972-4948 • Austin, (512)249-1900 • Birmingham, (205)678-2358 • Charlotte, (704)573-8446 • 

Chicago, (847)458-1500 • Cincinnati, (513)398-5500 • Cleveland, (330)467-1423 • Dallas, (972)620-6030 • Denver, (303)798-7778 • 
Detroit, (248)651-0500 • Eastern Canada, (450)433-1309 • Houston, (281)440-3074 • Indianapolis, (317)575-8932 • Kansas City, (913)897-3973 • 
Los Angeles, (714)935-2999 • Louisiana, (318)864-2864 • Maryland/Virginia, (215)345-8130 • Minneapolis/Manitoba, (952)892-9222 •  
Nashville, (615)264-6148 • New England, (603)882-1330 • New York/New Jersey/Philadelphia, (215)345-8130 • New York,Upstate, (716)438-0454 •
Ontario, (905)979-3507 • Orlando, (407)351-0737 • Phoenix, (602)298-6960 • Pittsburgh, (412)322-5004 • Portland, (503)245-9037 •
Raleigh/Greensboro, (336)766-9659 • St.Louis, (314)878-4600 • Sacramento, (707)425-1155 •  San Diego, (714)935-2999 • 
San Francisco, (408)434-1894 • Seattle, (425)222-4090 •  Tampa/St. Petersburg, (407)647-9052 • Tulsa, (918)496-2826 • 
Western Canada, (604)444-4881 • Wisconsin, North (920)993-2161 • Wisconsin, South (262)723-5990 

Asian Sales Offices:

Australia, +61 (3) 9335-6449 • China, +86 (21) 6277-2138 •  Japan, +81 (03) 5403-4688 •  Korea, +82 (02) 575-9804 • 

Malaysia, +60 (4) 641-5977 •  Singapore, +65 777-9488 • Taiwan, +886 (0) 7-288-5168  

European Sales Offices:

France, +33 (01) 3073-2425 •

Germany, +49 (0) 7253-9400-0 • Italy, +39 (02) 458-8841 • Sweden, +46 31 7014959 •  United Kingdom, +44 (0) 115-964-0777  

Latin American Sales Office:

Mexico, +52 (442) 217-6235

Отзывы: