Watlow F4T Install & Troubleshooting
•
37
•
Chapter 5 Troubleshooting
Indication
Description
Possible Cause(s)
Corrective Action
No heat/cool
action
Output does not
activate load
• Output function is incor-
rectly set
• Control mode is incor-
rectly set
• Algorithim is set off
• Output is incorrectly
wired
• Load, power or fuse is
open
• Control set point is incor-
rect
• Incorrect controller
model for application
• Set output function cor-
rectly
• Set control mode appro-
priately (Open vs Closed
Loop)
• Set heat/cool algorithim
to on/off or PID.
• Correct output wiring
• Correct fault in system
• Set control set point
in appropriate control
mode and check source
of set point: remote,
idle, profile, closed
loop, open loop
• Obtain correct control-
ler model for applica-
tion
No Display
No display indica-
tion
• Power to controller is off
• Fuse open
• Breaker tripped
• Safety interlock switch
open
• Separate system limit
control activated
• Wiring error
• Incorrect voltage to con-
troller
• Turn on power
• Replace fuse
• Reset breaker
• Close interlock switch
• Reset limit
• Correct wiring issue
• Apply correct voltage,
check part number