Terminal Definitions

Slot C

Terminal Function

Model

98

99

power input: ac or dc+

power input: ac or dc-

PM _L_ _ _ - AAAAB _ _

CF

CD

CE

Standard Bus EIA-485 common

Standard Bus EIA-485 T-/R-

Standard Bus EIA-485 T+/R+

PM _L_ _ _ - AAAAB _ _

Slot A

Input 1

T1

S1

R1

S2 (RTD) or c, 

S3 (RTD), thermocouple -, current - or 

volts -, thermistor

S1 (RTD), thermo or volts +, 

thermistor

Universal Sensor
input 1: all configurations

Outputs

Terminal Function

Configuration

1

2

X1

W1

Y1

common (Any switched dc output can 

use.)

dc- (open collector)

dc+

Switched dc/open collector, output 1: 

PM _L_ (C) _-_ AAAB _ _

L1

K1

J1

normally open

common

normally closed

Mechanical Relay 5 A, Form C, output 1: 

PM _L_ (E) _-_ AAAB _ _

L2

K2

normally open

common

Mechanical Relay 5 A, Form A, output 2: 

PM _L_ _ (J)-_ AAAB _ _ 

9 10

11 12

Power

Power

power 

power 

98
99

CF

CD
CE

Slot C 

fuse 

 

•  47 to 63 Hz
•  10VA maximum power consumption (PM3 and PM6)
•  14VA maximum power consumption (PM4, 8 and 9)

  

Low Power 

•  12 to 40V

Î

 (dc) 

•  20 to 28V

Å

 (ac) Semi Sig F47

  

High Power

• 85 to 264V

Å

 (ac)

•100 to 240V

Å

 (ac) Semi Sig F47

Ó

 

Warning:

Use National Electric (NEC) or other country-

specific standard wiring and safety practices when 

wiring and connecting this controller to a power 

source and to electrical sensors or peripheral 

devices. Failure to do so may result in damage 

to equipment and property, and/or injury or loss 

of life.

Note:

Maximum wire size termination and torque 

rating: 

• 0.0507 to 3.30 mm2 (30 to 12 AWG) single- 

  wire termination or two 1.31 mm2 (16 AWG) 

• 0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled differently, 

depending on the model number. 

Note:

To prevent damage to the controller, do not con-

nect wires to unused terminals. 

Note:

In the graphics below notice that the Slot A connector does not show labeling for the outputs. Labeling 

for Slot A outputs is based on the controller part number.

C

A

T1    S1    R1

Output 1

Output 2

CF   CD   CE

98    99

PM3

C

A

Output 

2

Output 

1

B

98
99

CF

CD

CE

T1
S1
R1

PM6

PM4

A

Output 

2

Output 

1

B

Output 

3
Output 

4

Input 

2

D

Digital I/O 7 - 12

E

Communications Car

d

C

98
99

CF

CD

CE

T1
S1
R1

A

Output 

2

Output 

1

B

D

E

C

98
99

CF

CD

CE

T1
S1
R1

PM9

PM8

C

E

A

Output 

2

Output 

1

B

Output 

3
Output 

4

Input 

2

T1
S1
R1

98
99

CF

CD

CE

D

Digital I/O 7 - 12

D

Note:

In the drawings below for each input notice that the Slot A connector labeling is identified.

Note:

When using a 2 wire RTD, jumper S1 and T1 together

Inputs

All inputs shown below represent input 1 (the only input) and are to be connected to slot A of the Limit 

Control. 

Process Volts and Amperes

•  4 to 20 mA @ 100 Ω input impedance

•  0 to 10V

Î

 (dc) @ 20 kΩ input impedance

•  Scalable

Resistance Temperature Detector (RTD)

•  Platinum, 100 Ω @ 0°C
•  Calibration to DIN curve (0.00385 Ω/Ω/°C)
•  20 Ω total lead resistance
•  RTD excitation current of 0.09 mA typical. 

Each ohm of lead resistance may affect the 

reading by 0.03°C.

•  For 3-wire RTDs, the S1 lead must be con

-

nected to R1.

•  For best accuracy use a 3-wire RTD to com

-

pensate for lead-length resistance. All three 

lead wires must have the same resistance.

Thermocouple

•  2 KΩ maximum source resistance
•  >20 MΩ input impedance
•  3 microampere open-sensor detection
•  Thermocouples are polarity sensitive. The 

negative lead must be connected to S1.

•  To reduce errors, the extension wire for ther

-

mocouples must be of the same alloy as the 

thermocouple.

Thermistor

•  >20 MΩ input impedance
•  3 microampere open-sensor detection

-

+

Thermocouple

S1
R1

T1
S1
R1

S1

S2

S3

RTD

2 or 3 Wire

-

+

-

+

S1
R1

T1
S1

Process
   Volts

 Process
Amperes

Thermistor

S1

R1

Содержание EZ-ZONE PM Express

Страница 1: ...proved by Factory Mutual as a Temperature Limit Device per FM Class 3545 standard See www fmglobal com Unit has been reviewed and approved by CSA International for use as Temperature Indicating Regula...

Страница 2: ...e blade of a screwdriver in the notch of the mounting collar assembly and push toward the panel while applying pressure to the face of the controller Don t be afraid to apply enough pressure to proper...

Страница 3: ...ot con nect wires to unused terminals Note In the graphics below notice that the Slot A connector does not show labeling for the outputs Labeling for Slot A outputs is based on the controller part num...

Страница 4: ...of outputs 1 and 2 Communications Activity Flashes when another device is communicating with this controller Upper Display On power up displays the process value otherwise displays the value of the p...

Страница 5: ...Appears if Always tC Thermocouple MA Milliamps dc uolT Volts dc r0 1H RTD 100 Lin Lin Linearization Set the linearization to match the thermocouple type wired to this input For example select H for a...

Страница 6: ...or Left Display Select parameter to display Appears if Always AC Pu Active Process Value none None loC Lockout Menu SEn Sensor Type Lin Linearization t C Thermistor Curve r r Resistance Range deC Deci...

Страница 7: ...lpha Techniques Beta THERM YSI Prompt tC 2 252K Curve A 2 2K3A 004 A 10K Curve A 10K3A 016 B 10K Curve C 10K4A 006 C Functional Operating Range Type B 50 to 1816 C 58 to 3301 F Type C 0 to 2315 C 32 t...

Страница 8: ...fo watlow co uk Website www watlow co uk From outside The United Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Pacific Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singapore 139...

Отзывы: