Watlow DIN-A-MITE Series Скачать руководство пользователя страница 3

L1

L2

3

Limit Control

Contacts

(if required)

Semiconductor

Fuses

4

Phase-to-phase
200V

Å

 (ac)

and above

Neutral

Phase-to-neutral
100V

Å

 (ac)

and above

V

Å

 (ac) Input:

4 to 20mA Input:

4.5 to 32V

Î

 (dc) Input:

Heater

2

1

5

6

7

8

9

10

+

5

6

5

6

+

Terminals 7 to 10

are not used.

Ground

L1

Limit Control

Contact

(if required)

Single-phase Output and Input Wiring

ç

WARNINGS:

Ó

1

WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN-A-MITE.
Failure to do so may result in damage to equipment and property, and/or injury or loss of life.

Ó

2

WARNING: Wiring examples show L2 in phase-to-phase, 200 V

Å

(ac) and above configuration. In phase-to-neutral, 100 V

Å

(ac) and

above  applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or
death.

Ó

3

WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on
this unit. Failure to do so could result in damage to equipment, and personal injury or death.

4 WARNING: Hot surface, do not touch the heat sink. Failure to follow this guideline could result in personal injury.

Ó

1

Ó

2

Ó

3

4

WATLOW DIN-A-MITE Style A User's Guide

3

NOTE:

Grounding

• Use a grounding conductor 

terminal plate (fork terminal) 
having upturned lugs or the 
equivalent to hold the wire in 
position. Maximum 6 mm

2

(10 

AWG) wire.

Fusing

• Recommended fusing options (see 

page 6) to meet 200KA SCCR, type 
1 and 2 approved.  All other fuse 
and SCR combinations are defaulted 

to 5KA SCCR per UL508A and NEC 

guidelines.

Torque Guidelines

• Properly torque line and load 

terminals to 1.4 Nm (12 in-lb).

• Retorque after 48 hours to 

minimize wire cold flow.

• Retorque line and load terminals 

every 3 to 6 months.

Содержание DIN-A-MITE Series

Страница 1: ...that your selections are consistent with your application inputs outputs alarms limits etc If the problem persists after checking the configuration of the controller you can get technical assistance f...

Страница 2: ...4 Grounding Hardware 6 Front Top Rail Release Tab Pull Down Zero Electrical Clearance Required Clearance for Air Flow and Bending Radius Clearance for Air Flow and Bending Radius Side 98 mm 3 87 in 50...

Страница 3: ...his guideline could result in personal injury or death 3 WARNING Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit Fai...

Страница 4: ...System Wiring Example 1 2 3 4 WATLOW DIN A MITE Style A User s Guide PM6C2CA ALAJAAA 98 99 CC CA CB B5 D6 D5 X1 W1 Y1 T1 S1 R1 L4 K4 T2 S2 R2 Coil L1 Neutral DA10 24C0 0000 5 6 7 8 9 10 Heater...

Страница 5: ...presses EMI on the power lines See figure below See Table 1 for the correct filter Description Crydom Watlow Filter Filter Single phase 230V ac 1F25 14 0019 Table 1 DIN A MITE EMI Filters WARNING The...

Страница 6: ...nubber circuit across its output Remove the RC snubber circuit before placing the DIN A MITE into service DC Contactor 4 5 to 32V dc maximum current 4 5V dc is 8 mA per leg Loop powered linear current...

Страница 7: ...EN 61000 4 11 2004 Voltage Dips Short Interruptions and Voltage Variations EN 61000 3 2 2005 Harmonic Current Emissions EN 61000 3 3 2005 Voltage Fluctuations and Flicker3 Notes 1Use of an external fi...

Страница 8: ...to people or property Failure to observe this warning could result in damage to property and or injury to death for personnel WARNING All filter installation and wiring must be performed by qualified...

Страница 9: ...Email info watlow co uk Website www watlow co uk From outside The United Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Pacific Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singa...

Отзывы: