WATLOW DIN-A-MITE Style C User's Manual
DIN-A-MITE
®
“C” Power Controller
WATLOW Electric Manufacturing Company
1241 Bundy Blvd. Winona, MN 55987 USA
Declares that the following products:
Designation:
DIN-A-MITE
®
“C” Power Control
Model Numbers:
DC(1, 2, 3, 8 or 9)(0, 1, 2, 3 or T) – (02, 12, 20, 24, 27, 40, 48 or 60) (CX, K1, K2, K3, FX, SX) -
(0, H or S)(followed by any 3 numbers or letters) X = any number 0 - 9
Classification:
Power Control, Installation Category III, Pollution degree 2, IP20
Rated Voltage:
24 to 600 V
~
(ac), 50 or 60 Hz
Meets the essential requirements of the following European Union Directives by using the relevant standards show
below to indicate compliance.
2004/108/EC Electromagnetic Compatibility Directive
EN 61326-1: 2013
Electrical equipment for measurement, control and laboratory use - EMC
requirements (Industrial Immunity, Class A
1,2,4
Emissions) Not for use in a Class B
environment without additional filtering.
EN 61000-4-2:2009
Electrostatic Discharge Immunity
EN 61000-4-3:2010
Radiated Field Immunity 10V/m 80 MHz- 1GHz, 3V/m 1.4GHz-2.7GHz
EN 61000-4-4:2012
Electrical Fast-Transient / Burst Immunity
EN 61000-4-5:2006
Surge Immunity (Reviewed to IEC 61000-4-5 2014)
EN 61000-4-6:2014
Conducted Immunity
EN 61000-4-11:2004
Voltage Dips, Short Interruptions and Voltage Variations
EN 61000-3-2:2009
Harmonic Current Emissions (Reviewed to IEC 61000-3-2 2014)
EN 61000-3-3:2013
Voltage Fluctuations and Flicker
3
≤
16A
EN 61000-3-11:2000
Voltage Fluctuations and Flicker
≤
75A with conditional connection
NOTES
1
Use of an external filter is required to comply with conducted emissions limits. See note 4 below.
2
A Line Impedance Stabilization Network (LISN) was used for conducted emissions measurements.
3
To comply with flicker requirements, command signal models FX and SX will require a reduced source impedance.
Cycle time on ON/OFF models CX, and K1, K2, K3 may need to be up to 175 seconds at 16A or have a reduced
source impedance.
2006/95/EC Low-Voltage Directive
EN 50178:1997
Electronic equipment for use in power installations.
Per 2012/19/EU W.E.E.E Directive Please Recycle Properly.
Compliant with 2011/65/EU RoHS2 Directive
4
Required External EMI Filters for DIN-A-MITE with More Than 6 Amp Loads
An external ElectroMagnetic Interference (EMI) filter must be used in conjunction with the DIN-A- MITE for loads in
excess of six amperes (6A) at 150 to 250 KHz. Watlow has verified that a tank filter will suppress EMI created by SCR
power controllers to comply with the conducted emissions limits.
ISO 9001since 1996.
Declaration of Conformity
DIN-A-MITE EMI Filters
Description
Crydom Filter
Watlow Filter
Single-phase, 230V
Å
(ac)
1F25
14-0019
Three-phase, 440V
Å
(ac)
3F20
14-0020