WATLOW DIN-A-MITE Style B User's Manual

DIN-A-MITE

®

“B” Power Controller

WATLOW Electric Manufacturing Company
1241 Bundy Blvd. Winona, MN 55987 USA

Declares that the following products:

Designation:

DIN-A-MITE® “B” Power Control

Model Numbers:

DB (1, 2, 3, 4, 8 or 9) 0 – (02, 24 or 60)(CX, FX, K1, K2, K3) – (0 or S)(followed by any 3 letters or 
numbers) (where X = any number 0-9)

Classification:

Power Control, Installation Category III, Pollution degree 2, IP20 

Rated Voltage:

24 to 600 V

~

(ac), 50 or 60 Hz

Meets the essential requirements of the following European Union Directives by using the relevant standards show below to
indicate compliance.

2004/108/EC Electromagnetic Compatibility Directive

EN 61326-1: 2013

Electrical equipment for measurement, control and laboratory use - EMC requirements 
(Industrial Immunity, Class A

1,2,4

Emissions) Not for use in a Class B environment without 

additional filtering.

EN 61000-4-2:2009

Electrostatic Discharge Immunity

EN 61000-4-3:2010

Radiated Field Immunity 10V/m 80 MHz- 1GHz, 3V/m 1.4GHz-2.7GHz 

EN 61000-4-4:2012

Electrical Fast-Transient / Burst Immunity

EN 61000-4-5:2006

Surge Immunity (Reviewed to IEC 61000-4-5 2014) 

EN 61000-4-6:2014

Conducted Immunity

EN 61000-4-11:2004

Voltage Dips, Short Interruptions and Voltage Variations

EN 61000-3-2:2009

Harmonic Current Emissions (Reviewed to IEC 61000-3-2 2014) 

EN 61000-3-3:2013

Voltage Fluctuations and Flicker

3  

≤ 

16A

EN 61000-3-11:2000

Voltage Fluctuations and Flicker

≤ 

75A with conditional connection

NOTES

1

Use of an external filter is required to comply with conducted emissions limits.  See note 4 below.

2

A Line Impedance Stabilization Network (LISN) was used for conducted emissions measurements.

3

To comply with flicker requirements, command signal models F0 and F1 will require a reduced source impedance. Cycle time
on ON/OFF models CX, and K1, K2, K3 may need to be up to 175 seconds at 16A or have a reduced source impedance.

2006/95/EC Low-Voltage Directive

EN 50178:1997

Electronic equipment for use in power installations.

Per 2012/19/EU W.E.E.E Directive           Please Recycle Properly.

Compliant with 2011/65/EU RoHS2 Directive

4

Required External EMI Filters for DIN-A-MITE with More Than 6 Amp Loads

An external ElectroMagnetic Interference (EMI) filter must be used in conjunction with the DIN-A- MITE for loads in excess of
six amperes (6A) at 150 to 250 KHz. Watlow has verified that a tank filter will suppress EMI created by SCR power controllers
to comply with the conducted emissions limits.

Declaration of Conformity

A

N

Breaker or f

u

sed

disconnect

Semicond

u

ctor F

u

se

Heater

2 3

5 6

Filter

5A

PE

A protecti

v

e earth (PE)

connection is re

qu

ired

PE

A

Semicond

u

ctor

 F

u

ses

1 2 3

4 5 6

6

4

5

Heater

Filter

5A

5A

5A

C

B

Alternate

Figure 2 - Tank filter,

three-phase, 440v

Breaker or 

f

u

sed disconnect

A protecti

v

e earth (PE)

 connection is re

qu

ired

A third semicond

u

ctor

f

u

se is not needed 

w

ith

 a t

w

o-leg DI

N

-A-MITE

DIN-A-MITE EMI Filters

Description

Crydom Filter

Watlow Filter

Single-phase, 230V

Å 

(ac)

1F25

14-0019

Three-phase, 440V

Å 

(ac)

3F20

14-0020

ISO 9001since 1996.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание DB10-02C0-0000

Страница 1: ...nstall electrical equipment This DIN A MITE product is capable of switching up to 40 amps single phase 33 amps 3 phase 2 leg and 22 amps 3 phase 3 leg at 600V ac See the output rating curve in the spe...

Страница 2: ...00 of span 4 3 to 19 7mA Temperature stability is less than 0 15 C change Alarm not available on multizone models Shorted SCR Alarm Option Alarm state when the input command signal off and a 10 A or m...

Страница 3: ...Table Model Current at 50 C 122 F DB10 35A DB20 DB80 25A DB30 DB90 17A Note Recommended fusing options to meet 200KA SCCR type 1 and 2 approved All other fuse and SCR combinations are defaulted to 5K...

Страница 4: ...ins vertically 1 1 2 Mount Dismount Front Allowance for 8 fastener metric M4 Grounding screw 6 Allowance for 8 fastener metric M4 DIN EN 50022 35 mm by 7 5 mm rail clipping distance 34 7 mm 1 366 in t...

Страница 5: ...13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac Input 7 8 9 10 11 12 13 Zone 1 V dc Input Zone 2 V dc Input Zone 3 V dc Input 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac...

Страница 6: ...al injury or death NOTE Use a grounding conductor terminal plate fork terminal having upturned lugs or the equivalent to hold the wire in position Maximum 6 mm2 10 AWG wire Torque Guidelines Properly...

Страница 7: ...ountry specific standard wiring practices to install and operate the DIN A MITE Failure to do so may result in damage to equipment and property and or injury or loss of life NOTE If you plan to wire m...

Страница 8: ...r each DIN A MITE used Torque Guidelines Properly torque line and load terminals to 1 4 Nm 12 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 mon...

Страница 9: ...the alternative latching circuit section below V 13 14 Triac RY1 Coil Reset Switch RY1A L1 L2 RY1B Normally open Common Normally closed External alarm relay contacts set A External alarm relay contac...

Страница 10: ...connection NOTES 1 Use of an external filter is required to comply with conducted emissions limits See note 4 below 2 A Line Impedance Stabilization Network LISN was used for conducted emissions measu...

Страница 11: ...G All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to properly suppress EMI however...

Страница 12: ...n shipment Your P O number Detailed description of the problem Any special instructions Name and phone number of person returning the product 2 Prior approval and an RMA number from the Customer Servi...

Отзывы: