D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
111
Input High Signal
l
01 Input high
r
signal 100.0%
For a process input, enter the input signal level that corresponds to the value for the
Input range high
parameter. The high signal is a percentage of the full scale input range.
Values:
-99.8 to 999.9 (-998 to 9999) percent of full scale. This value must be greater than the value
for
Input low signal
. Values in parentheses are for communications.
Default:
100.0% (1000)
Decimal Placement for DeviceNet™:
Decimal Placement for Percentage Values on page 46
DeviceNet™ Object:
Input (64 hex)
Input Range Low
l
01 Input range
r
low
b
0
For a process input, enter the low process variable for input scaling purposes. This value will be
displayed when the input signal is at the level set for
Input low signal
.
This value and the value for
Input low signal
together define one of the points on the scaling
function’s conversion line. Setting Up a Process Input on page 69
Values:
Any value between the minimum process variable for the selected display format (see Table
6.10 on the previous page) and the value for
Input range high
.
Default:
0
Decimal Placement for DeviceNet™:
Decimal Placement for Numeric Values on page 46
DeviceNet™ Object:
Input (64 hex)
Input Low Signal
l
01 Input low
r
signal
b
.0%
For a process input, enter the input signal level that corresponds to the low process variable you
entered for the
Input range low
parameter. The low signal is a percentage of the full scale input
range.
Values:
-99.9 to 999.8 (-999 to 9998) percent of full scale. This value must be less than the value for
Input high signal
. Values in parenthesis are for communications.
Default:
0