Minimum Input
Enter the lowest value of the process variable to be retransmitted. This value is expressed in the
same engineering units as the input loop.
If the process variable falls below the minimum, the output will stay at the minimum value.
ALARM
02 HEAT RETRANS
MIN INP? 1000
Selectable values:
Any value in the input loop’s range.
Minimum Output
Enter the output value (0 to 100%) that corresponds to the minimum input.
If you select a minimum output value other than 0%, the output will never drop below
MIN OUT
,
even if the process variable drops below the
MIN INP
that you specified.
ALARM
02 HEAT RETRANS
MIN OUT%? 0%
Selectable values:
0
to
100%
.
Maximum Input
Enter the highest value of the process variable to be retransmitted. This value is expressed in the
same engineering units as the input loop.
If the process variable goes above the maximum, the output will stay at the maximum value.
ALARM
02 HEAT RETRANS
MAX INP? 10000
Selectable values:
Any value in the input loop’s range.
By adjusting the maximum and minimum inputs, you can scale the output appropriately.